WEB-202-XPR;WEB-202-XPR-GW (WEB-202-XPR with wireless modem);WEB-202-XPR-O (WEB-202-XPR with open license);WEB-202-XPR-GWO (WEB-202-XPR with wireless modem and open license)
Primary Control Unit
WEB-202-XPR
Date Last Saved: 3/5/2012 9:06:11 AM
Product Name(s):
|
WEB-202-XPR;WEB-202-XPR-GW (WEB-202-XPR with wireless modem);WEB-202-XPR-O (WEB-202-XPR with open license);WEB-202-XPR-GWO (WEB-202-XPR with wireless modem and open license)
|
Product Description:
|
Embedded controller and server platform that provides integrated control, supervision, data logging, alarming, scheduling, network management functions, and a graphical user interface.
|
Product Application(s):
|
Used for control, monitoring, and energy management in small facilities.
Used for providing distributed control and monitoring in multi-site applications.
|
|
Point Quantity
|
Characteristics
|
Analog Input (AI):
|
N.A.
|
|
Digital Input (DI):
|
N.A.
|
|
Universal Input (AI or DI):
|
8
|
10K Thermistor 0-10 V 0-20 mA Dry contact
|
Analog Output (AO):
|
4
|
0-10 V
|
Digital Output (DO):
|
4
|
Relay (24 VAC/30 VDC)
|
Universal Output (UO):
|
|
|
Other:
|
|
|
Control Unit Model #: | AI | DI | UI | DO | AO | UO | Other |
WEB-202-XPR
|
|
|
8
|
4
|
4
|
|
|
|
A/D Converter Resolution
|
|
D/A Converter Resolution
|
|
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
|
|
Indicating status LED on each output?
|
|
Integral Flow Sensor?
|
N.A.
|
Integral Damper Actuator?
|
N.A.
|
Can controller accept occupant override from thermostat?
|
N.A.
|
Can controller accept occupancy sensor input?
|
N.A.
|
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
|
(2) ethernet ports @ 10/100 Mbps (1) EIA-232 port (1) EIA-485 port
|
External Communication Ports, Speeds and Access Devices
|
Optional FTT10 LON adapter (card only) Optional FTT10 LON adapter (card and driver) Optional RS-232 port adapter Optional dual port RS-485 adapter (electronically isolated) Optional modem card
|
Additional Information (Optional)
|
|
Network Accessing Capabilities via Controller
|
|
Controller Access Devices
|
|
Zone-Based Interface Access
|
|
Zone Interface Hardware
|
|
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e.
'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
|
Microprocessor(s)
|
AMCC PowerPC 405; 250 MHz processor
|
Clock Type
|
|
Clock Synchronization
|
yes
|
Volatile Memory (RAM) Capacity
|
128 MB SDRAM
|
Volatile Memory (RAM) Uses
|
|
|
Is Volatile Memory Supported By Battery?
|
yes
|
Battery Type(s)
|
NiMh battery; Optional external 12VDC sealed lead acid battery
|
Battery Life
|
3 month minimum
|
Backup Battery Operating Time
|
5 minutes is typical
|
Non-Volatile Memory Capacity (EEPROM/Flash)*
|
64 MB serial flash
|
Non-Volatile Memory Uses
|
|
Additional Information
|
|
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly
impact system performance.
|
Can trend data be stored in this controller?
|
yes
|
How many total trend values can be stored?
|
information not provided
|
What is the controllers role in trending?
|
trending source
|
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller?
|
|
When full, does controller automatically send up trend data, overwrite data, or stop logging data?
|
information not provided
|
Programming Method(s)
|
WEBs-AX
|
Resident vs Non-Resident Program Execution
|
information not provided
|
Scheduling
|
|
Resident Energy Management
|
|
Specific Pre-Programmed Algorithms Available
|
|
Additional Programming Functions
|
|
DDC Loops (P, PI, PID)
|
information not provided
|
Automatic PID Tuning Feature
|
information not provided
|
Automatical-Dial Alarm Support
|
information not provided
|
Does controller perform multiple retries and buffer/store alarm until connection is made?
|
information not provided
|
Are multiple destinations possible?
|
yes
|
Upon controller power loss or hardware failure:
|
Are network communications affected?
|
no
|
Is loss recognized on/by the network and alarm reported?
|
yes
|
DO and AO response?
|
|
Volatile memory functions?
|
|
Upon restoration of power does the controller:
|
Auto-reboot without operator intervention?
|
information not provided
|
Automatically reset/synchronize the clock?
|
information not provided
|
Update all monitored functions?
|
information not provided
|
Generate an alarm if backup battery is dead?
|
information not provided
|
Upon network or communications failure does controller:
|
Continue to operate standalone?
|
yes
|
Operate with last global settings or user-specified value?
|
N.A.
|
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
|
information not provided
|
Does network automatically reconfigure upon restoration?
|
information not provided
|
Does network store 'loss of communications' alarm with time of event?
|
information not provided
|
Additional Information (optional)
|
|
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
|
Processor failure?
|
information not provided
|
Internal hardware failure?
|
information not provided
|
Open/shortened sensor?
|
information not provided
|
Others?
|
|
|
Control Enclosure
|
plastic; wall mounted chassis
|
Power Supply Required
|
24V AC/DC
|
Voltage
|
information not provided
|
VA
|
information not provided
|
Surge Protection
|
|
Underwriters Laboratories
|
UL 916 C-UL listed to Canadian Standards Association
|
FCC
|
Part 15 Class A
|
CE
|
yes
|
LonMark Certified
|
|
BACnet (BTL) Certified
|
|
Other
|
|