DDC Online direct digital controls
Honeywell - WEBs-AX  

NXS-AX-FL;NXS-AX-FLO;NXS-AX-HD;NXS-AX-HDO;

Supervisory Interface Devices
NXS-AX
Date Last Saved: 8/12/2008 2:08:21 PM

Product Name(s): NXS-AX-FL;NXS-AX-FLO;NXS-AX-HD;NXS-AX-HDO;
Product Description: This product line is developed on the Niagra Framework and includes UPS power supply, embedded Windows XP, Web User Interface, oBIX driver, and LON over twisted pair.
Product Application(s): Specifically designed for commercial and light industrial applications.
Point Quantity Characteristics
Analog Input (AI): N.A.
Digital Input (DI): N.A.
Universal Input (AI or DI): N.A.
Analog Output (AO): N.A.
Digital Output (DO): N.A.
Universal Output (UO): N.A.
Other:
A/D Converter Resolution
8 bit
10 bit
12 bit
16 bit
Other Information not provided
D/A Converter Resolution
6 bit
8 bit
10 bit
No Analog Output
Other Information not provided
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
No
Both AO and DO
DO Only
Other Information not provided
Indicating status LED on each output?
No
AO and DO
AO Only
DO Only
Other Information not provided
Integral Flow Sensor? N.A.
Integral Damper Actuator? N.A.
Can controller accept occupant override from thermostat? N.A.
Can controller accept occupancy sensor input? N.A.
Expander Boards N.A.
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
2 Ethernet Ports - 10/100 Mbps
1 RSA-232 Port
1 RS-485 non isolated port
4 USB Ports
1 Lonworks FTT10A Port (78K)
External Communication Ports, Speeds and Access Devices
Additional Information (Optional)
Network Accessing Capabilities via Controller
Access controller only
Access controller plus additional controllers on network segment / LAN
Access all controllers on system
No access available on this controller
Other
Controller Access Devices
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Zone-Based Interface Access
Zone Interface Hardware
Zone-Mounted touchpad (thermostat or stand-alone display)
HID (proprietary device)
PDA (3rd party HID, with software)
Laptop/PC
none
Other
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
Functions Available Through Field Interface**:View ParamsChange ParamsChange
Programs/Logic
O&M SupportTAB/Cx Support
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Microprocessor(s) Intel Celeron 650 Mhz
Clock Type
Powered, battery-backed
Battery powered
Powered, no battery backing
None
Other
Clock Synchronization Yes with webstation or internet connection
Volatile Memory (RAM) Capacity 512 MB SDRam
Volatile Memory (RAM) Uses
RAM use unrestricted
RAM use restricted as shown below
Information Not Provided
Program Execution / Calculation storage
Data / Trends / Alarms storage
Configuration / Parameter storage
Control Programming storage
Others
Is Volatile Memory Supported By Battery? 5 minites is typical
Battery Type(s) Lithium
Battery Life Information not provided
Backup Battery Operating Time 5 minutes typical, shut down begins within 10 seconds of writing to flash memory or hard drive.
Non-Volatile Memory Capacity (EEPROM/Flash)* 1 GB Serial Flash or 40 GB Hard Drive
Non-Volatile Memory Uses
Data / Trends / Alarms / Calculation Storage Yes
Configuration / Parameter Storage Yes
Control Programming Storage Yes
Controller Operating System Yes
Other
Additional Information
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.
Can trend data be stored in this controller? Yes
How many total trend values can be stored? Determined by resource count
What is the controllers role in trending? Trending source
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller? Yes
When full, does controller automatically send up trend data, overwrite data, or stop logging data? Automatically sends all data to WebStation
Programming Method(s) WEBsPRO-AX
Resident vs Non-Resident Program Execution Information not Provided
Scheduling
Resident/Supervisory. This controller supervises the scheduling of other controllers.
Resident/Stand Alone. This controller contains its own schedule.
Non-Resident. This controller is dependent upon another controller for its schedule.
None. This controller has no scheduling features.
Other
Resident Energy Management
Energy management algorithms for this controller can be custom programmed
Pre-programmed/built-in algorithms available, and are fully editable using custom programming
Pre-Programmed/built-in with limited editing via template-based programming
Controller is not typically used for energy management functions
Others
Specific Pre-Programmed Algorithms Available
None (custom programming only)
None (not applicable)
Optimal Start/Optimal Stop
Peak Demand Limiting/Load Shedding
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.)
Other
Additional Energy Management functions are resident at SI
Additional Programming Functions
DDC Loops (P, PI, PID) Yes (P,PI,PID)
Automatic PID Tuning Feature No
Automatical-Dial Alarm Support External modem
Does controller perform multiple retries and buffer/store alarm until connection is made? Yes
Are multiple destinations possible? Yes
Upon controller power loss or hardware failure:
Are network communications affected? No
Is loss recognized on/by the network and alarm reported? Yes, by WebStation
DO and AO response?
Outputs fail to a user pre-specified position
Outputs fail to a normal (unpowered) position
Outputs fail to last position
Other
Volatile memory functions?
Lost
Retained for life of backup battery
Other
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Yes
Automatically reset/synchronize the clock? Yes
Update all monitored functions? Yes
Generate an alarm if backup battery is dead? Yes
Upon network or communications failure does controller:
Continue to operate standalone? Yes
Operate with last global settings or user-specified value? N.A.
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
Yes
Does network automatically reconfigure upon restoration? Yes
Does network store 'loss of communications' alarm with time of event? Yes
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? Yes
Internal hardware failure? N.A.
Open/shortened sensor? N.A.
Others? N.A.
 
Control Enclosure Heavy duty stell chassis
Power Supply Required
Voltage 100-240 VAC
47-63 Hz
VA 2A Max/115V and
1A Max/230V
Surge Protection Integral UPS
Underwriters Laboratories UL 916, C-UL listed to Canadian Standards Association (CSA)
FCC Part 15 Class A
CE Yes
LonMark Certified
Yes
No
No - but LonWorks compatible
Information not provided
BACnet (BTL) Certified
Yes
No
Not submitted for testing
Information not provided
Other