DDC Online direct digital controls
Honeywell - Light Commercial Building Solution (LCBS)  

Excel 15 W7760A;Excel 15 W7760C

Primary Control Unit
Excel 15
Date Last Saved: 7/12/2011 3:59:40 PM

Product Name(s): Excel 15 W7760A;Excel 15 W7760C
Product Description: The Excel 15 W7760A & W7760C are part of the Light Commercial Building Systems (LCBS) product line. They can be used to monitor and control Honeywell HVAC equipment in a distributed network. It performs energy management, scheduling, trending, and alarm handling functions. It can also perform PID control using on-board I/O and/or remote I/O devices.
Product Application(s): Can be used for heat pump systems, boilers, chillers, packaged RTU's, and built-up RTU's in small building applications.
Point Quantity Characteristics
Analog Input (AI): see below 0-10V
Resistive
Digital Input (DI): see below dry contacts
Universal Input (AI or DI): N.A.
Analog Output (AO): see below 0-20mA
Digital Output (DO): see below 24 Vac Triac
Universal Output (UO): N.A.
Other:
Control Unit Model #:AIDIUIDOAOUOOther
W7760A 8 4 8 2
W7760C 8 8 8 6
A/D Converter Resolution
8 bit
10 bit
12 bit
16 bit
Other Information not provided
D/A Converter Resolution
6 bit
8 bit
10 bit
No Analog Output
Other Information not provided
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
No
Both AO and DO
DO Only
Other Information not provided
Indicating status LED on each output?
No
AO and DO
AO Only
DO Only
Other
Integral Flow Sensor? N.A.
Integral Damper Actuator? N.A.
Can controller accept occupant override from thermostat? N.A.
Can controller accept occupancy sensor input? N.A.
Expander Boards Excel 10 Remote Input/Output, maximum of three
Expansion Device Model #AIDIUIDOAOUOOther
Excel 10 W7761A 6 4 8
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
LonTalk port to Honeywell E-Bus @ 78 Kbps
External Communication Ports, Speeds and Access Devices E-Bus network access jack for connection of laptop/PC to Excel 15 using serial LonTalk adapter (SLTA)
Additional Information (Optional) 7760A has modem interface possible through Comm port
Network Accessing Capabilities via Controller
Access controller only
Access controller plus additional controllers on network segment / LAN
Access all controllers on system
No access available on this controller
Other
Controller Access Devices
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other Information not provided
Zone-Based Interface Access
Zone Interface Hardware
Zone-Mounted touchpad (thermostat or stand-alone display)
HID (proprietary device)
PDA (3rd party HID, with software)
Laptop/PC
none
Other
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
Functions Available Through Field Interface**:View ParamsChange ParamsChange
Programs/Logic
O&M SupportTAB/Cx Support
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other Information not provided
Microprocessor(s)
Clock Type
Powered, battery-backed
Battery powered
Powered, no battery backing
None W7760C
Other W7760A powered with 60 hour capacitor back-up
Clock Synchronization 7760A - Real-time clock runs on either 50/60 Hz or it's internal crystal. The RTC tracks time of day, day of week, month, and year (including leap year) and synchronizes the time/date for all other network devices. Daylight savings time can be enabled/disabled.
7760C - No Clock
Volatile Memory (RAM) Capacity 3072 bytes - for trend data 50 events - for alarms
Volatile Memory (RAM) Uses
RAM use unrestricted
RAM use restricted as shown below
Information Not Provided
Program Execution / Calculation storage
Data / Trends / Alarms storage
Configuration / Parameter storage
Control Programming storage
Others
Is Volatile Memory Supported By Battery? 6-hour capacitor is standard
Lithium battery is optional
Battery Type(s) Optional - lithium
Battery Life Information not provided
Backup Battery Operating Time Information not provided
Non-Volatile Memory Capacity (EEPROM/Flash)* Information not provided
Non-Volatile Memory Uses
Data / Trends / Alarms / Calculation Storage
Configuration / Parameter Storage
Control Programming Storage
Controller Operating System
Other Information not provided
Additional Information
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.
Can trend data be stored in this controller? 7760A - Yes
7760C - No
How many total trend values can be stored? 7760A - Trending of up to 16 inputs with a maximum trend sample space of 3072 bytes. Each trend point includes: input point, sampling interval, type of trend (one-shot, periodic, delta, or continuous), and start/stop date/time. A runtime log is can also be maintained for up to 15 digital inputs or outputs.
What is the controllers role in trending? Information not provided
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller?
When full, does controller automatically send up trend data, overwrite data, or stop logging data? Information not provided
Programming Method(s) RapidZone;
LonSpec
Resident vs Non-Resident Program Execution Information not provided
Scheduling
Resident/Supervisory. This controller supervises the scheduling of other controllers. 7760A
Resident/Stand Alone. This controller contains its own schedule.
Non-Resident. This controller is dependent upon another controller for its schedule.
None. This controller has no scheduling features. 7760C
Other
Resident Energy Management
Energy management algorithms for this controller can be custom programmed 7760A
Pre-programmed/built-in algorithms available, and are fully editable using custom programming
Pre-Programmed/built-in with limited editing via template-based programming
Controller is not typically used for energy management functions
Others
Specific Pre-Programmed Algorithms Available
None (custom programming only)
None (not applicable)
Optimal Start/Optimal Stop
Peak Demand Limiting/Load Shedding
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.)
Other Information not provided
Additional Energy Management functions are resident at SI
Additional Programming Functions
DDC Loops (P, PI, PID) PID
Automatic PID Tuning Feature Information not provided
Automatical-Dial Alarm Support 7760A - Alarm prioritization, routing, multi-site dial out and history log
7760C - No
Does controller perform multiple retries and buffer/store alarm until connection is made? 7760A - Yes
Are multiple destinations possible? 7760A - Yes
Upon controller power loss or hardware failure:
Are network communications affected? No
Is loss recognized on/by the network and alarm reported? Information not provided
DO and AO response?
Outputs fail to a user pre-specified position
Outputs fail to a normal (unpowered) position
Outputs fail to last position
Other Information not provided
Volatile memory functions?
Lost
Retained for life of backup battery
Other
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Information not provided
Automatically reset/synchronize the clock? 7760A - Yes
Update all monitored functions? Information not provided
Generate an alarm if backup battery is dead? Information not provided
Upon network or communications failure does controller:
Continue to operate standalone? Information not provided
Operate with last global settings or user-specified value? N.A.
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
Information not provided
Does network automatically reconfigure upon restoration? Information not provided
Does network store 'loss of communications' alarm with time of event? Information not provided
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? Information not provided
Internal hardware failure? Information not provided
Open/shortened sensor? Information not provided
Others?
 
Control Enclosure Subbase and snap-on cover/electronics
Power Supply Required
Voltage 20-30 Vac, 50/60 Hz
VA 20-100 VA (with digital outputs)
Surge Protection No
Underwriters Laboratories UL916 for Energy Management computing devices (Class II device)
FCC Part 15, Sub-Part J, Class A
CE Level A
LonMark Certified
Yes
No
No - but LonWorks compatible
Information not provided
BACnet (BTL) Certified
Yes
No
Not submitted for testing
Information not provided
Other