DDC Online direct digital controls
Invensys - I/A Series  

Package Equipment Module (PEM)

Secondary Control Units
Package Equipment Module (PEM)
Date Last Saved: 8/2/2011 4:32:27 PM

Product Name(s): Package Equipment Module (PEM)
Product Description: The PEM is a pre-programmed (configurable) fixed 6 input/10 output application-specific controller that resides on the secondary ASD network. Programming can be modified for custom applications if needed
Product Application(s): The PEM is designed for small unitary applications such as unit ventilators, fan coil units, packaged rooftop units, and air and water source heat pumps. Most often applied as a network controller on the proprietary ASD Bus managed by the Global Control Module (GCM). Will also function as a stand-alone controller. The PEM has a variety of zone temperature sensor options.
Point Quantity Characteristics
Analog Input (AI): 4 4 - 20 ma
0 - 5 Vdc
Setpoint adjustment input from TS-90250 sensor. Dry contacts may be tied across input
Thermistor TS-5700 sensor or equivalent, or as a dry contact.
Digital Input (DI): 2 2 Dry contact of can be used for pulse @ 1 pulse per second
Universal Input (AI or DI): N.A.
Analog Output (AO): 2 0-20 mA programmable range
Digital Output (DO): 8 SPST (Form A) Relays: 30 VA @ 24Vac
Universal Output (UO):
Other:
A/D Converter Resolution
8 bit
10 bit
12 bit
16 bit
Other
D/A Converter Resolution
6 bit
8 bit
10 bit
No Analog Output
Other
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
No
Both AO and DO
DO Only
Other
Indicating status LED on each output?
No
AO and DO
AO Only
DO Only
Other
Integral Flow Sensor? N.A.
Integral Damper Actuator? N.A.
Can controller accept occupant override from thermostat? N.A.
Can controller accept occupancy sensor input? N.A.
Expander Boards N.A.
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
(1) - Proprietary to secondary ASD Bus @ 19.2 kbps (peer-to-peer)
External Communication Ports, Speeds and Access Devices (1) - Proprietary port for Personal System Interface (PSI) hand held device. Port is screw terminal on the PEM controller board, or plug in from proprietary wall sensors.
(1) - Serial port
Additional Information (Optional)
Network Accessing Capabilities via Controller
Access controller only
Access controller plus additional controllers on network segment / LAN
Access all controllers on system
No access available on this controller
Other Information not provided
Controller Access Devices
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other Information not provided
Zone-Based Interface Access Information not provided
Zone Interface Hardware
Zone-Mounted touchpad (thermostat or stand-alone display)
HID (proprietary device)
PDA (3rd party HID, with software)
Laptop/PC
none
Other Information not provided
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
Functions Available Through Field Interface**:View ParamsChange ParamsChange
Programs/Logic
O&M SupportTAB/Cx Support
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other Information not provided
Microprocessor(s) 80C198 @ 7 MHz (16 bit)
Clock Type
Powered, battery-backed
Battery powered
Powered, no battery backing
None
Other
Clock Synchronization Not applicable
Volatile Memory (RAM) Capacity 8 kB RAM
Volatile Memory (RAM) Uses
RAM use unrestricted
RAM use restricted as shown below
Information Not Provided
Program Execution / Calculation storage
Data / Trends / Alarms storage
Configuration / Parameter storage
Control Programming storage
Others
Is Volatile Memory Supported By Battery? No
Battery Type(s) N.A.
Battery Life N.A.
Backup Battery Operating Time N.A.
Non-Volatile Memory Capacity (EEPROM/Flash)* 2 kB EEPROM
Non-Volatile Memory Uses
Data / Trends / Alarms / Calculation Storage
Configuration / Parameter Storage
Control Programming Storage
Controller Operating System
Other
Additional Information
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.
Can trend data be stored in this controller? No
How many total trend values can be stored? Not applicable
What is the controllers role in trending? None - trend points are called by and stored at the GCM
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller?
When full, does controller automatically send up trend data, overwrite data, or stop logging data? N.A.
Programming Method(s) Uses Network 8000 Object Block programming. 'Object Blocks' are available for many common DDC control routines, and custom Object Blocks can be written and used in programming when required. Block parameters and values are left as template-based inputs by the user.
Resident vs Non-Resident Program Execution Local control loop logic is resident at the controller. Schedules, trending, data control, and global point sharing requires GCM supervisory interface.
Scheduling
Resident/Supervisory. This controller supervises the scheduling of other controllers.
Resident/Stand Alone. This controller contains its own schedule.
Non-Resident. This controller is dependent upon another controller for its schedule.
None. This controller has no scheduling features.
Other
Resident Energy Management
Energy management algorithms for this controller can be custom programmed
Pre-programmed/built-in algorithms available, and are fully editable using custom programming
Pre-Programmed/built-in with limited editing via template-based programming
Controller is not typically used for energy management functions
Others
Specific Pre-Programmed Algorithms Available
None (custom programming only)
None (not applicable)
Optimal Start/Optimal Stop
Peak Demand Limiting/Load Shedding
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.)
Other
Additional Energy Management functions are resident at SI
Additional Programming Functions
DDC Loops (P, PI, PID) PID
Automatic PID Tuning Feature No
Automatical-Dial Alarm Support Information not provided
Does controller perform multiple retries and buffer/store alarm until connection is made? Information not provided
Are multiple destinations possible? No
Upon controller power loss or hardware failure:
Are network communications affected? Yes
Is loss recognized on/by the network and alarm reported?
DO and AO response?
Outputs fail to a user pre-specified position
Outputs fail to a normal (unpowered) position
Outputs fail to last position
Other
Volatile memory functions?
Lost
Retained for life of backup battery
Other
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Yes
Automatically reset/synchronize the clock? N.A.
Update all monitored functions? Yes
Generate an alarm if backup battery is dead? N.A.
Upon network or communications failure does controller:
Continue to operate standalone? Yes
Operate with last global settings or user-specified value? N.A.
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
Information not provided
Does network automatically reconfigure upon restoration? Yes - Communications between controllers is automatically restored upon network reconnection
Does network store 'loss of communications' alarm with time of event? Yes
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? Information not provided
Internal hardware failure? Information not provided
Open/shortened sensor? Information not provided
Others?
 
Control Enclosure Information not provided
Power Supply Required
Voltage 24 Vac
VA 20 VA
Surge Protection Provided
Underwriters Laboratories UL 916 PAZX (Energy Management)

UUKL 864 UDTZ (Smoke Control)
FCC Part 15, Sub-Part B, Class A
CE
LonMark Certified
Yes
No
No - but LonWorks compatible
Information not provided
BACnet (BTL) Certified
Yes
No
Not submitted for testing
Information not provided
Other