DDC Online direct digital controls
Automated Logic - WebCTRL  

SE Line

Primary Control Unit
SE Line
Date Last Saved: 7/11/2011 11:40:36 AM

Product Name(s): SE Line
Product Description: The SE Line provides control for single equipment applications.
Product Application(s): SE controllers can be used in rooftop units, mechanical rooms, equipment closets, or weather tight location.
Point Quantity Characteristics
Analog Input (AI): N.A.
Digital Input (DI): N.A.
Universal Input (AI or DI): See Below 0-5 Vdc
0-10 Vdc
0-20 mA
Thermistor (10k Ohm Type II)
1k Ohm RTD (Platinum, Nickel, or Balco)
Dry Contact.
20HZ Pulse counting
Analog Output (AO): See Below 0-20 Vdc
0-20 mA
Digital Output (DO): See Below Relay contact (3A max @ 24 Vac) configured normally open with hand-off-auto switches.
Universal Output (UO):
Other:
Control Unit Model #:AIDIUIDOAOUOOther
SE6104 10 6 4
SE6166 16 6 6
A/D Converter Resolution
8 bit
10 bit
12 bit
16 bit
Other
D/A Converter Resolution
6 bit
8 bit
10 bit
No Analog Output
Other
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
No
Both AO and DO
DO Only
Other
Indicating status LED on each output?
No
AO and DO
AO Only
DO Only
Other
Integral Flow Sensor? No
Integral Damper Actuator? No
Can controller accept occupant override from thermostat? Yes
Can controller accept occupancy sensor input? Yes (dry contact, 0-5 Vdc, 0-10Vdc, 0-20mA)
Expander Boards None
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
(1)-BACnet ARCnet at 156 kbps or BACnet MS/TP
External Communication Ports, Speeds and Access Devices (1)-Rnet port supports the RS room sensors
(1)-BACview6 local operator interface.
Additional Information (Optional)
Network Accessing Capabilities via Controller
Access controller only
Access controller plus additional controllers on network segment / LAN
Access all controllers on system
No access available on this controller
Other
Controller Access Devices
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Zone-Based Interface Access The BACview 6 is a local interface keypad device and supports the following features:

* Rnet capable device supported on the SE6104, ME Line, and WebZone
* Up to 2 BACviews on each Rnet (referencing the same control program)
* 4 x 40 screen display size
Zone Interface Hardware
Zone-Mounted touchpad (thermostat or stand-alone display)
HID (proprietary device)
PDA (3rd party HID, with software)
Laptop/PC
none
Other
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
Functions Available Through Field Interface**:View ParamsChange ParamsChange
Programs/Logic
O&M SupportTAB/Cx Support
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Microprocessor(s) 16-bit microprocessor with ARCnet communictaion co-processor
Clock Type
Powered, battery-backed
Battery powered
Powered, no battery backing
None
Other
Clock Synchronization Time synchronization occurs periodically through broadcasts from the WebCTRL server, and from the BACnet Router on each network segment.
Volatile Memory (RAM) Capacity Module contains only non-volatile and flash memory.
Volatile Memory (RAM) Uses
RAM use unrestricted
RAM use restricted as shown below
Information Not Provided
Program Execution / Calculation storage
Data / Trends / Alarms storage
Configuration / Parameter storage
Control Programming storage
Others N.A.
Is Volatile Memory Supported By Battery? N.A.
Battery Type(s) N.A.
Battery Life N.A.
Backup Battery Operating Time N.A.
Non-Volatile Memory Capacity (EEPROM/Flash)* 1 MByte non-volatile battery-backed RAM, 1 MByte Flash memory, 16-bit memory bus.
Non-Volatile Memory Uses
Data / Trends / Alarms / Calculation Storage
Configuration / Parameter Storage
Control Programming Storage
Controller Operating System
Other
Additional Information
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.
Can trend data be stored in this controller? Yes.
How many total trend values can be stored? Information not provided
What is the controllers role in trending? Information not provided
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller?
When full, does controller automatically send up trend data, overwrite data, or stop logging data? The module can be configured to stop, deliver, or overwrite.
Programming Method(s) SE line controllers are fully graphically programable.
Resident vs Non-Resident Program Execution All graphical programs reside in the controller.
Scheduling
Resident/Supervisory. This controller supervises the scheduling of other controllers.
Resident/Stand Alone. This controller contains its own schedule.
Resident/Stand Alone. This controller contains its own schedule.
Non-Resident. This controller is dependent upon another controller for its schedule.
None. This controller has no scheduling features.
Other
Resident Energy Management
Energy management algorithms for this controller can be custom programmed
Energy management algorithms for this controller can be custom programmed
Pre-programmed/built-in algorithms available, and are fully editable using custom programming
Pre-Programmed/built-in with limited editing via template-based programming
Controller is not typically used for energy management functions
Others
Specific Pre-Programmed Algorithms Available
None (custom programming only)
None (not applicable)
Optimal Start/Optimal Stop
Optimal Start/Optimal Stop
Peak Demand Limiting/Load Shedding
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.)
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.)
Other
Additional Energy Management functions are resident at SI
Additional Programming Functions
DDC Loops (P, PI, PID) Supports PID loop logic.
Automatic PID Tuning Feature No
Automatical-Dial Alarm Support Yes
Does controller perform multiple retries and buffer/store alarm until connection is made? Yes
Are multiple destinations possible? Yes
Upon controller power loss or hardware failure:
Are network communications affected? No
Is loss recognized on/by the network and alarm reported? Yes
DO and AO response?
Outputs fail to a user pre-specified position
Outputs fail to a normal (unpowered) position
Outputs fail to last position
Other Information Not Provided
Volatile memory functions?
Lost
Retained for life of backup battery
Other N.A.
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Yes
Automatically reset/synchronize the clock? Yes
Update all monitored functions? Yes
Generate an alarm if backup battery is dead? Yes
Upon network or communications failure does controller:
Continue to operate standalone? Yes
Operate with last global settings or user-specified value? N.A.
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
Yes
Does network automatically reconfigure upon restoration? Yes
Does network store 'loss of communications' alarm with time of event? Information not provided
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? Information not provided
Internal hardware failure? Information not provided
Open/shortened sensor? Information not provided
Others?
 
Control Enclosure Control modules are constructed with an aluminum cover.
Power Supply Required
Voltage 24 Vac +/- 10%, 26 Vdc (25 V min, 30 V max), 50 to 60 Hz.
VA 20 VA.
Surge Protection Built-in surge and transient protection circuitry for power, communication, inputs, and outputs.
Underwriters Laboratories 916 (Canadian Std C22.2 No. 205-M1983)
FCC Part 15 - Subpart B-Class A
CE YES
LonMark Certified
Yes
No
No - but LonWorks compatible
Information not provided
BACnet (BTL) Certified
Yes
No
Not submitted for testing
Information not provided
Other