DDC Online direct digital controls
American Auto-Matrix - AspectFT  

SBC-V3Tb; SBC-V3Td; NB-V3Tb; NB-V3Td

Secondary Control Units
SBC-V3T and NB-V3T
Date Last Saved: 2/22/2012 3:11:35 PM

Product Name(s): SBC-V3Tb; SBC-V3Td; NB-V3Tb; NB-V3Td
Product Description: SBC controllers are members of the Evolution Series line of controls and NB controllers are members of the Native BACnet line of controls. Application specific VAV air handling unit controllers. Designed to control duct static pressure or airflow in a VAV AHU. Can be used to convert a constant volume AHU to VAV AHU.
Product Application(s): The SBC-V3Tb and NB-V3Tb modulate a system's bypass damper to maintain duct static pressure. The SBC-V3Td and NB-V3Td control the zone damper and uses a discharge air temperature algorithm.
Point Quantity Characteristics
Analog Input (AI): N.A.
Digital Input (DI): N.A.
Universal Input (AI or DI): See below 0-20 mA
0-10 Vdc
0-1 mega ohm
Analog Output (AO): See below 0-10 VDC
Digital Output (DO): See below Relay (1 amp)
Universal Output (UO): N.A.
Other:
Control Unit Model #:AIDIUIDOAOUOOther
SBC-V3Tb 0 5 5 4 1
SBC-V3Td 0 1 0 0
NB-V3Tb 0 5 5 4 1
NB-V3Td 0 1 0 0
A/D Converter Resolution
8 bit
10 bit
12 bit
16 bit
Other 15 bit
D/A Converter Resolution
6 bit
8 bit
10 bit
No Analog Output
Other
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
No
Both AO and DO
DO Only
Other
Indicating status LED on each output?
No
AO and DO
AO Only
DO Only
Other
Integral Flow Sensor? V3Tb: Yes, Static Pressure Sensor
V3Td: No
Integral Damper Actuator? Yes
Can controller accept occupant override from thermostat? Yes
Can controller accept occupancy sensor input? Yes
Expander Boards
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
SBC Line: (1) EIA-485 Public Unitary Protocol (PUP) port @ up to 38.4 kbps.

NB Line: (1) EIA-485 BACnet MS/TP port @ up to 38.4 kbps.
External Communication Ports, Speeds and Access Devices (1) RJ-11 for connection of laptop or hand-held interface device via zone-based port at zone stat as described under 'Operator Interfaces' below
Additional Information (Optional)
Network Accessing Capabilities via Controller
Access controller only
Access controller plus additional controllers on network segment / LAN
Access all controllers on system
No access available on this controller
Other
Controller Access Devices
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted) SBC-STAT3
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Zone-Based Interface Access Thermostat with optional RJ-11 port for access to controller via laptop or hand-held interface
Zone Interface Hardware
Zone-Mounted touchpad (thermostat or stand-alone display) SBC-STAT
HID (proprietary device)
PDA (3rd party HID, with software)
Laptop/PC
none
Other
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
Functions Available Through Field Interface**:View ParamsChange ParamsChange
Programs/Logic
O&M SupportTAB/Cx Support
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted) SBC-STAT3
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Microprocessor(s)
Clock Type
Powered, battery-backed V3Tb. Optional on V3Td.
Battery powered
Powered, no battery backing
None
Other
Clock Synchronization V3Tb can broadcast time synchronization.
Volatile Memory (RAM) Capacity Information not provided
Volatile Memory (RAM) Uses
RAM use unrestricted
RAM use restricted as shown below
Information Not Provided
Program Execution / Calculation storage
Data / Trends / Alarms storage
Configuration / Parameter storage
Control Programming storage
Others
Is Volatile Memory Supported By Battery? No
Battery Type(s)
Battery Life
Backup Battery Operating Time
Non-Volatile Memory Capacity (EEPROM/Flash)* Has flash memory for control application.
Non-Volatile Memory Uses
Data / Trends / Alarms / Calculation Storage
Configuration / Parameter Storage
Control Programming Storage
Controller Operating System
Other
Additional Information
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.
Can trend data be stored in this controller? No
How many total trend values can be stored? None. Feature available through SF1 or SAGEMAX
What is the controllers role in trending? None. Feature available through SF1 or SAGEMAX
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller?
When full, does controller automatically send up trend data, overwrite data, or stop logging data? No. Feature available through SF1 or SAGEMAX
Programming Method(s) Programmed using menu-driven SOLOPro/NB-Pro software.
Resident vs Non-Resident Program Execution All program execution is designed to be controller resident although the SAGEMAX and/or SF1 can be programmed to perform/supervise unit controller functions. Controller-resident program execution is ensured by selecting the proper controller for the application.
Scheduling
Resident/Supervisory. This controller supervises the scheduling of other controllers. V3Tb
Resident/Stand Alone. This controller contains its own schedule.
Non-Resident. This controller is dependent upon another controller for its schedule. Controllers can receive broadcast schedules.
None. This controller has no scheduling features.
Other
Resident Energy Management
Energy management algorithms for this controller can be custom programmed
Pre-programmed/built-in algorithms available, and are fully editable using custom programming
Pre-Programmed/built-in with limited editing via template-based programming
Controller is not typically used for energy management functions
Others
Specific Pre-Programmed Algorithms Available
None (custom programming only)
None (not applicable)
Optimal Start/Optimal Stop
Peak Demand Limiting/Load Shedding
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.) V3Tb
Other
Additional Energy Management functions are resident at SI
Additional Programming Functions
DDC Loops (P, PI, PID) V3Tb: PID
Automatic PID Tuning Feature No
Automatical-Dial Alarm Support No. Feature available through SF1 or SAGEMAX
Does controller perform multiple retries and buffer/store alarm until connection is made? No. Feature available through SF1 or SAGEMAX
Are multiple destinations possible? No. Feature available through SF1 or SAGEMAX
Upon controller power loss or hardware failure:
Are network communications affected? Information not provided
Is loss recognized on/by the network and alarm reported? Yes. Continuous controller diagnostics results in an alarm at the SAGEMAX or SF1 in the event that the control program stops or aborts.
DO and AO response?
Outputs fail to a user pre-specified position
Outputs fail to a normal (unpowered) position
Outputs fail to last position
Other
Volatile memory functions?
Lost
Retained for life of backup battery
Other
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Yes
Automatically reset/synchronize the clock? Yes (V3Tb only)
Update all monitored functions? Yes
Generate an alarm if backup battery is dead? No
Upon network or communications failure does controller:
Continue to operate standalone? Yes
Operate with last global settings or user-specified value? N.A.
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
Yes
Does network automatically reconfigure upon restoration? Yes
Does network store 'loss of communications' alarm with time of event? No
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? Information not provided
Internal hardware failure? Information not provided
Open/shortened sensor? Yes
Others?
 
Control Enclosure Information not provided
Power Supply Required
Voltage 22-25 Vac 50/60 Hz
VA 10 VA
Surge Protection 5A Fuse load protection, PTC controller protection
Underwriters Laboratories UL 916 PAZX (Energy Management)

UL 873 listed, Component-temperature-indicating and regulating equipment (XAPX2)
FCC Part 15, Class B Computing Device
CE Complies with CE directives and standards
LonMark Certified
Yes
No
No - but LonWorks compatible
Information not provided
BACnet (BTL) Certified
Yes NB line
No SBC Line
Not submitted for testing
Information not provided
Other