DDC Online direct digital controls
American Auto-Matrix - AspectFT  

MC1

Secondary Control Units
MC1 Unit Controller
Date Last Saved: 2/22/2012 3:10:29 PM

Product Name(s): MC1
Product Description: 15-point application specific controller with firmware based control functions
Product Application(s): Small to medium air handlers including variable speed, fan tracking, and pressurization control schemes Fan coil units Unit heaters Unit ventilators Heat pumps Hot and chilled water setpoint reset Pressure dependent VAV boxes
Point Quantity Characteristics
Analog Input (AI): N.A.
Digital Input (DI): N.A.
Universal Input (AI or DI): 8 0-5 Vdc
0-20 mA
10k thermistor

Analog Output (AO): 3 0-10 Vdc
Digital Output (DO): 4 Triac, 24 Vac/1 Amp
Universal Output (UO):
Other:
A/D Converter Resolution
8 bit
10 bit
12 bit
16 bit
Other two of the universal inputs are 15 bit
D/A Converter Resolution
6 bit
8 bit
10 bit
No Analog Output
Other 15 bit
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
No
Both AO and DO
DO Only
Other
Indicating status LED on each output?
No
AO and DO
AO Only
DO Only
Other
Integral Flow Sensor? N.A.
Integral Damper Actuator? N.A.
Can controller accept occupant override from thermostat? N.A.
Can controller accept occupancy sensor input? N.A.
Expander Boards
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
(1) EIA-485 Public Unitary Protocol (PUP) port @ up to 38.4 kbps.
External Communication Ports, Speeds and Access Devices (1) RJ-11 for connection of hand-held interface device via zone-based port at zone stat as described under 'Operator Interfaces' below
Additional Information (Optional)
Network Accessing Capabilities via Controller
Access controller only
Access controller plus additional controllers on network segment / LAN
Access all controllers on system
No access available on this controller
Other
Controller Access Devices
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted) SoloView
Handheld Interface Device (proprietary device) SoloTool
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Zone-Based Interface Access The SOLOTool hand held interface device can be used to program and for viewing and changing parameters.
Zone Interface Hardware
Zone-Mounted touchpad (thermostat or stand-alone display)
HID (proprietary device)
PDA (3rd party HID, with software)
Laptop/PC
none
Other
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
Functions Available Through Field Interface**:View ParamsChange ParamsChange
Programs/Logic
O&M SupportTAB/Cx Support
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted) SoloView
Handheld Interface Device (proprietary device) SoloTool
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Microprocessor(s) Information not provided
Clock Type
Powered, battery-backed
Battery powered
Powered, no battery backing
None
Other
Clock Synchronization None
Volatile Memory (RAM) Capacity RAM stores setpoints, overrides, and other operator adjustable settings. Other information not provided.
Volatile Memory (RAM) Uses
RAM use unrestricted
RAM use restricted as shown below
Information Not Provided
Program Execution / Calculation storage
Data / Trends / Alarms storage
Configuration / Parameter storage
Control Programming storage
Others
Is Volatile Memory Supported By Battery? No
Battery Type(s) No battery
Battery Life No battery
Backup Battery Operating Time No battery
Non-Volatile Memory Capacity (EEPROM/Flash)* EEPROM stores the application program and default setpoints, I/O configuration, high/low alarms, etc. Other information not provided.
Non-Volatile Memory Uses
Data / Trends / Alarms / Calculation Storage
Configuration / Parameter Storage setpoints, parameters, user settings, schedules, etc.
Control Programming Storage
Controller Operating System
Other
Additional Information
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.
Can trend data be stored in this controller? No
How many total trend values can be stored? None. Feature available through AspectFt Matrix Area Controller or SAGEMAX
What is the controllers role in trending? None. Feature available through AspectFt Matrix Area Controller or SAGEMAX
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller?
When full, does controller automatically send up trend data, overwrite data, or stop logging data? No. Feature available through AspectFt Matrix Area Controller or SAGEMAX
Programming Method(s) Programmed using menu-driven SOLOPro software. The SOLOTool hand held operating device can also be used for programming.
Resident vs Non-Resident Program Execution All program execution is designed to be controller resident although the SAGEMAX and/or AspectFt Matrix Area Controller can be programmed to perform/supervise unit controller functions. Controller-resident program execution is ensured by selecting the proper controller for the application.
Scheduling
Resident/Supervisory. This controller supervises the scheduling of other controllers.
Resident/Stand Alone. This controller contains its own schedule.
Non-Resident. This controller is dependent upon another controller for its schedule.
None. This controller has no scheduling features.
Other This controller can also receive scheduling commands from the SAGEMAX or AspectFt Matrix Area Controller
Resident Energy Management
Energy management algorithms for this controller can be custom programmed
Pre-programmed/built-in algorithms available, and are fully editable using custom programming
Pre-Programmed/built-in with limited editing via template-based programming
Controller is not typically used for energy management functions
Others
Specific Pre-Programmed Algorithms Available
None (custom programming only)
None (not applicable)
Optimal Start/Optimal Stop
Peak Demand Limiting/Load Shedding
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.)
Other See below
Additional Energy Management functions are resident at SI
Additional Programming Functions The MC1 can perform runtime totalization.
DDC Loops (P, PI, PID) PID
Automatic PID Tuning Feature No
Automatical-Dial Alarm Support No. Feature available through AspectFt Matrix Area Controller or SAGEMAX
Does controller perform multiple retries and buffer/store alarm until connection is made? No. Feature available through AspectFt Matrix Area Controller or SAGEMAX
Are multiple destinations possible? No. Feature available through AspectFt Matrix Area Controller or SAGEMAX
Upon controller power loss or hardware failure:
Are network communications affected? No
Is loss recognized on/by the network and alarm reported? Yes. Continuous controller diagnostics results in an alarm at the SAGEMAX or AspectFt Matrix Area Controller in the event that the control program stops or aborts.
DO and AO response?
Outputs fail to a user pre-specified position
Outputs fail to a normal (unpowered) position
Outputs fail to last position
Other
Volatile memory functions?
Lost
Retained for life of backup battery
Other Upon restoration of power the controller operates at default settings stored in EEPROM that were defined during initial configuration.
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Yes
Automatically reset/synchronize the clock? No
Update all monitored functions? Yes
Generate an alarm if backup battery is dead? No
Upon network or communications failure does controller:
Continue to operate standalone? Yes
Operate with last global settings or user-specified value? N.A.
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
Yes
Does network automatically reconfigure upon restoration? Yes
Does network store 'loss of communications' alarm with time of event? Yes
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? Yes
Internal hardware failure? Yes
Open/shortened sensor? Yes
Others?
 
Control Enclosure Steel chassis
Power Supply Required
Voltage 24 Vac 50/60 Hz
VA 20 VA max
Surge Protection Fused at 1 amp
Underwriters Laboratories UL-listed 916 (Enclosed Energy Management Equipment)

UL-recognized 873, Temperature indicating and regulating equipment.
FCC Part 15, Class B Computing Device
CE PTC load protection.Inputs: R-C filter.
LonMark Certified
Yes
No
No - but LonWorks compatible
Information not provided
BACnet (BTL) Certified
Yes
No
Not submitted for testing
Information not provided
Other