ASI Controls - ASIC  

ASIC/1-6000

Secondary Control Units
ASIC/1-6000
Date Last Saved: 5/9/2006 10:49:38 AM

Product Name(s): ASIC/1-6000
Product Description: The ASIC/1-6000 is a preprogrammed VAV controller with an integrated actuator. Controller maintains space temperature by varying the air volume.
Product Application(s): Pressure independent (ASIC/1-6000) and pressure dependent (ASIC/1-6000-PD) Variable Air Volume (VAV) boxes and Fan-Powered VAV boxes. Also available as a -MB model without an actuator.
Point Quantity Characteristics
Analog Input (AI): N.A.
Digital Input (DI): N.A.
Universal Input (AI or DI): 6 0-5 VDC, 10 bit, 0.1% full scale
3 kohm thermistor
Analog Output (AO): 1 0-10 VDC, 20 mA
Digital Output (DO): 5 Solid state switch
24 VAC, 1 A, MOV protected
Universal Output (UO): N.A.
Other:
Control Unit Model #:AIDIUIDOAOUOOther
ASIC/1-6000 6 5 1
A/D Converter Resolution
8 bit
10 bit
12 bit
16 bit
Other
D/A Converter Resolution
6 bit
8 bit
10 bit
No Analog Output
Other Information not provided
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
No
Both AO and DO
DO Only
Other
Indicating status LED on each output?
No
AO and DO
AO Only
DO Only
Other
Integral Flow Sensor? Yes.
Integral Damper Actuator? Yes.
Can controller accept occupant override from thermostat? Yes.
Can controller accept occupancy sensor input? No.
Expander Boards None.
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
(1) EIA-485 port with ASI proprietary protocol @ up to 19.2 kbps
External Communication Ports, Speeds and Access Devices (1) RJ-45 port for connection to WS-0x1 zone sensor
Additional Information (Optional)
Network Accessing Capabilities via Controller
Access controller only
Access controller plus additional controllers on network segment / LAN
Access all controllers on system
No access available on this controller
Other
Controller Access Devices
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Zone-Based Interface Access Controller has 8-position jack for RJ-45 cable to WS-051 Zone Thermostat. WS-0x1 has RJ-12 jack for connection of SINC/1-1030 which connects to a PC/Laptop.
Zone Interface Hardware
Zone-Mounted touchpad (thermostat or stand-alone display)
HID (proprietary device)
PDA (3rd party HID, with software)
Laptop/PC
none
Other
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
Functions Available Through Field Interface**:View ParamsChange ParamsChange
Programs/Logic
O&M SupportTAB/Cx Support
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Microprocessor(s) Intel 8051 Family
Clock Type
Powered, battery-backed
Battery powered
Powered, no battery backing
None
Other
Clock Synchronization Time based features can only be used when controller is connected to a network and can be synchronized by a time broadcast by the SINC/3-3000 or ASIC/2 controller.
Volatile Memory (RAM) Capacity Information not provided
Volatile Memory (RAM) Uses
RAM use unrestricted
RAM use restricted as shown below
Information Not Provided
Program Execution / Calculation storage
Data / Trends / Alarms storage
Configuration / Parameter storage
Control Programming storage
Others
Is Volatile Memory Supported By Battery? No
Battery Type(s) None
Battery Life N.A.
Backup Battery Operating Time N.A.
Non-Volatile Memory Capacity (EEPROM/Flash)* Information not provided
Non-Volatile Memory Uses
Data / Trends / Alarms / Calculation Storage
Configuration / Parameter Storage
Control Programming Storage
Controller Operating System
Other
Additional Information
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.
Can trend data be stored in this controller? Yes
How many total trend values can be stored? Two Trends 96 byte values at 15 min interval(Typical).
Trend 1 Zone Temp {Default)
Trend 2 Supply Air Temp (Typical)
What is the controllers role in trending? Writes data to static memory
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller? Information not provided.
When full, does controller automatically send up trend data, overwrite data, or stop logging data? Rolls over at end of day
Programming Method(s) No programming is necessary. A preprogrammed personality is selected depending on application.
Resident vs Non-Resident Program Execution Resident
Scheduling
Resident/Supervisory. This controller supervises the scheduling of other controllers.
Resident/Stand Alone. This controller contains its own schedule. Scheduled changes in setpoint can only occur when a time message is broadcast to the controller over the network.
Non-Resident. This controller is dependent upon another controller for its schedule.
None. This controller has no scheduling features.
Other
Resident Energy Management
Energy management algorithms for this controller can be custom programmed
Pre-programmed/built-in algorithms available, and are fully editable using custom programming
Pre-Programmed/built-in with limited editing via template-based programming
Controller is not typically used for energy management functions
Others Information not provided.
Specific Pre-Programmed Algorithms Available
None (custom programming only)
None (not applicable)
Optimal Start/Optimal Stop
Peak Demand Limiting/Load Shedding Setpoint Spread and Shed
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.)
Other Preprogrammed sequences are built in for different applications.
Additional Energy Management functions are resident at SI
Additional Programming Functions
DDC Loops (P, PI, PID) Pre-tuned PI algorithm
Automatic PID Tuning Feature No, Controller comes pretuned and user can manually change Throttling Range.
Automatical-Dial Alarm Support No
Does controller perform multiple retries and buffer/store alarm until connection is made? Controller sets alarm until it clears. The controller can be polled by the System controller which can send the alarm.
Are multiple destinations possible? N.A.
Upon controller power loss or hardware failure:
Are network communications affected? No. Skips off-line controller.
Is loss recognized on/by the network and alarm reported? Front end will typically report off-line if it does not receive a response
DO and AO response?
Outputs fail to a user pre-specified position
Outputs fail to a normal (unpowered) position
Outputs fail to last position
Other
Volatile memory functions?
Lost
Retained for life of backup battery
Other
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Resumes normal operation.
Automatically reset/synchronize the clock? Accepts synchronize from SINC/3 or ASIC/2. Assumes Occupied if not synchronized.
Update all monitored functions? Trends continue.
Generate an alarm if backup battery is dead? N.A.
Upon network or communications failure does controller:
Continue to operate standalone? Continues to operate with internal schedule if time synchronized, otherwise it assumes occupied conditions and setpoints.
Operate with last global settings or user-specified value? N.A.
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
Yes.
Does network automatically reconfigure upon restoration? No.
Does network store 'loss of communications' alarm with time of event? User interface can show off-line.
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? No.
Internal hardware failure? No.
Open/shortened sensor? Input Faults are set. If zone temperature is in fault the outputs are off.
Others?
 
Control Enclosure Enclosure and actuator provided.
Power Supply Required
Voltage 24 VAC +/- 15%
VA 6 VA (plus loads)
Surge Protection 1/2 A Polyswitch
Underwriters Laboratories UL 916, Open Energy Management
FCC Meets FCC Requirements
CE Meets CE Requirements
LonMark Certified
Yes
No
No - but LonWorks compatible
Information not provided
BACnet (BTL) Certified
Yes
No
Not submitted for testing
Information not provided
Other