DDC Online direct digital controls
Reliable Controls - MACH-System  

SMART-Space Controller

Secondary Control Units
SMART-Space Controller
Date Last Saved: 8/13/2009 8:45:08 AM

Product Name(s): SMART-Space Controller
Product Description: The SMART-Space Controller is a fully programmable space controller.
Product Application(s): The SMART-Space Controller is designed for small point-count, standalone, or distributed network applications.
Point Quantity Characteristics
Analog Input (AI): See Below
Digital Input (DI): N.A.
Universal Input (AI or DI): See Below 0-10 VDC
4-20 mA
Thermistor
Dry Contact
Analog Output (AO): N.A.
Digital Output (DO): N.A.
Universal Output (UO): See Below 0-12 VDC
24 VAC @ 0.5 A
Other: N.A.
Control Unit Model #:AIDIUIDOAOUOOther
SSC 1 2 2
SSCE 1 3 2 2
SSCP 1 3 2 2
A/D Converter Resolution
8 bit
10 bit
12 bit
16 bit
Other
D/A Converter Resolution
6 bit
8 bit
10 bit
No Analog Output
Other 12 bit
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
No
Both AO and DO
DO Only
Other Override via keypad
Indicating status LED on each output?
No
AO and DO
AO Only
DO Only
Other Status via keypad
Integral Flow Sensor? N.A.
Integral Damper Actuator? N.A.
Can controller accept occupant override from thermostat? N.A.
Can controller accept occupancy sensor input? N.A.
Expander Boards N.A.
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
(1) BACnet MS/TP Slave
EIA-485 @ 76800 baud max
External Communication Ports, Speeds and Access Devices RJ11 jack allows connection to PC via X-Port-2 converter.
Additional Information (Optional)
Network Accessing Capabilities via Controller
Access controller only
Access controller plus additional controllers on network segment / LAN
Access all controllers on system
No access available on this controller
Other
Controller Access Devices
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Zone-Based Interface Access PC connection using X-Port-2 converter
Zone Interface Hardware
Zone-Mounted touchpad (thermostat or stand-alone display)
HID (proprietary device)
PDA (3rd party HID, with software)
Laptop/PC
none
Other
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
Functions Available Through Field Interface**:View ParamsChange ParamsChange
Programs/Logic
O&M SupportTAB/Cx Support
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Microprocessor(s) Information not provided.
Clock Type
Powered, battery-backed
Battery powered
Powered, no battery backing
None
Other Information not provided.
Clock Synchronization Information not provided.
Volatile Memory (RAM) Capacity Information not provided.
Volatile Memory (RAM) Uses
RAM use unrestricted
RAM use restricted as shown below
Information Not Provided
Program Execution / Calculation storage
Data / Trends / Alarms storage
Configuration / Parameter storage
Control Programming storage
Others Information not provided.
Is Volatile Memory Supported By Battery? Information not provided.
Battery Type(s) Information not provided.
Battery Life Information not provided.
Backup Battery Operating Time 72 hour backup
10 years for database
Non-Volatile Memory Capacity (EEPROM/Flash)* Information not provided.
Non-Volatile Memory Uses
Data / Trends / Alarms / Calculation Storage
Configuration / Parameter Storage
Control Programming Storage
Controller Operating System
Other Information not provided.
Additional Information
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.
Can trend data be stored in this controller? Yes.
How many total trend values can be stored? Up to 2 trend logs can be stored consisting of 8 points per trend.
What is the controllers role in trending? Collection and storage for local points
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller? Pulled
When full, does controller automatically send up trend data, overwrite data, or stop logging data? Overwrites data
Programming Method(s) The SMART-Space Controller can be programmed using a PC connected via the network or locally via X-Port-2 converter.
Resident vs Non-Resident Program Execution SMART-Space points can be controlled by resident or non-resident programs.
Scheduling
Resident/Supervisory. This controller supervises the scheduling of other controllers.
Resident/Stand Alone. This controller contains its own schedule.
Non-Resident. This controller is dependent upon another controller for its schedule.
None. This controller has no scheduling features.
Other
Resident Energy Management
Energy management algorithms for this controller can be custom programmed
Pre-programmed/built-in algorithms available, and are fully editable using custom programming
Pre-Programmed/built-in with limited editing via template-based programming
Controller is not typically used for energy management functions
Others
Specific Pre-Programmed Algorithms Available
None (custom programming only)
None (not applicable)
Optimal Start/Optimal Stop
Peak Demand Limiting/Load Shedding
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.)
Other Information not provided.
Additional Energy Management functions are resident at SI
Additional Programming Functions
DDC Loops (P, PI, PID) Standard P, PI, or PID controller for closed loop control
Automatic PID Tuning Feature Information not provided.
Automatical-Dial Alarm Support Information not provided.
Does controller perform multiple retries and buffer/store alarm until connection is made? Information not provided.
Are multiple destinations possible? Information not provided.
Upon controller power loss or hardware failure:
Are network communications affected? Information not provided.
Is loss recognized on/by the network and alarm reported? Information not provided.
DO and AO response?
Outputs fail to a user pre-specified position
Outputs fail to a normal (unpowered) position
Outputs fail to last position
Other Information not provided.
Volatile memory functions?
Lost
Retained for life of backup battery
Other Information not provided.
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Yes
Automatically reset/synchronize the clock? Yes
Update all monitored functions? Yes
Generate an alarm if backup battery is dead? Information not provided.
Upon network or communications failure does controller:
Continue to operate standalone? Yes
Operate with last global settings or user-specified value? N.A.
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
Yes
Does network automatically reconfigure upon restoration? Yes
Does network store 'loss of communications' alarm with time of event? Information not provided.
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? Information not provided.
Internal hardware failure? Information not provided.
Open/shortened sensor? Information not provided.
Others?
 
Control Enclosure Plastic cover . Back plate with terminals allow wiring before plugging in controller.
Power Supply Required Yes
Voltage 24 VAC/VDC
VA 10 VA
Surge Protection Yes, MOV protected
Underwriters Laboratories UL 916 Open Energy Management
FCC Information not provided.
CE Information not provided.
LonMark Certified
Yes
No
No - but LonWorks compatible
Information not provided
BACnet (BTL) Certified
Yes
No
Not submitted for testing
Information not provided
Other