DSC-1616/H/E; DSC-1212/H/E; DSC-1146E; DSC-1180E

Primary Control Unit
DSC-1616/H/E, DSC-1212/H/E, DSC-1146E, DSC-1180E
Date Last Saved: 7/29/2011 10:41:56 AM

Product Name(s): DSC-1616/H/E; DSC-1212/H/E; DSC-1146E; DSC-1180E
Product Description: DSC-1616/H/E The DSC-1616 has 16 Universal Inputs and 16 Analog Outputs. This controller comes with optional monitored HOA switches and can also be ordered with a built in 10Base-T Ethernet port. DSC-1212/H/E The DSC-1212 has 12 Universal Inputs and 12 Analog Outputs. This controller comes with optional monitored HOA switches and can also be ordered with a built in 10Base-T Ethernet port. DSC-1146E The DSC-1146 has 11 Universal Inputs, 4 Analog Outputs and 6 Digital Outputs. This controller comes with optional monitored HOA switches and can also be ordered with a built in 10Base-T Ethernet port. DSC-1180E The DSC-1180 has 11 Universal Inputs and 8 Analog Outputs. This controller comes with optional monitored HOA switches and can also be ordered with a built in 10Base-T Ethernet port.
Product Application(s): DSC-1616/H/E: Medium-to-Large point count applications including AHUs, boilers, chillers, etc. Network router between Ethernet and BACnet MS/TP and/or BACnet PTP. DSC-1212/H/E: Medium point count applications including AHUs, boilers, chillers, etc. Network router between Ethernet and BACnet MS/TP and/or BACnet PTP. DSC-1146E: Medium point count applications including AHUs, boilers, chillers, etc. Network router between Ethernet and BACnet MS/TP and/or BACnet PTP. DSC-1180E: Medium point count applications including AHUs, boilers, chillers, etc. Network router between Ethernet and BACnet MS/TP and/or BACnet PTP.
Point Quantity Characteristics
Analog Input (AI): N.A.
Digital Input (DI): N.A.
Universal Input (AI or DI): See Below Jumper Selectable

0-5 Volt DC
0-10 Volt DC
10 Kohm
4-20 mA
Analog Output (AO): See Below 0 to 10 Volt DC @ 20 mA max.
Digital Output (DO): N.A.
Universal Output (UO):
Other:
Control Unit Model #:AIDIUIDOAOUOOther
DSC 1616/H/E 16 16
DSC-1212/H/E 12 12
DSC-1280/H/E 12 8
A/D Converter Resolution
8 bit
10 bit
12 bit
16 bit
Other
D/A Converter Resolution
6 bit
8 bit
10 bit
No Analog Output
Other
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
No
Both AO and DO
DO Only
Other
Indicating status LED on each output?
No
AO and DO
AO Only
DO Only
Other
Integral Flow Sensor? N.A.
Integral Damper Actuator? N.A.
Can controller accept occupant override from thermostat? N.A.
Can controller accept occupancy sensor input? N.A.
Expander Boards Expansion Boards are available in a variety of I/O configurations.
Expansion Device Model #AIDIUIDOAOUOOther
DFM-200 2
DFM-202 2 2
DFM-220 2 2
DFM-400 4
DFM-404 4 4
DFM-440 4 4
DFM-1600 16
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
BACnet MS/TP over EIA-485 @ 76.8 Kbps (optional 9.6,19.2,38.4 kbps)

Optional BACnet/IP or BACnet over Ethernet 10Base-T @ 10 Mbps

BACnet PTP over EIA-232 @ 9600 default (optional 19200, 38400)
External Communication Ports, Speeds and Access Devices (2) EIA-485 @ 76.8 kbps default (optional 9.6, 19.2, 38.4 kbps)

(1) EIA-232 (for OWS/Modem) @ 9.6 kbps default (optional 19.2, 38.4 kbps)

RJ-11 Service Port for Network-wide controller access
Additional Information (Optional) Controllers are capable of BACnet/IP or BACnet over Ethernet if controller is provided with optional Ethernet jack.
Network Accessing Capabilities via Controller
Access controller only
Access controller plus additional controllers on network segment / LAN
Access all controllers on system
No access available on this controller
Other
Controller Access Devices
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Zone-Based Interface Access RJ-11 Service Port on both controllers and Network Sensors (DNS-24) provide BACnet MS/TP communication access to entire controller network.
Zone Interface Hardware
Zone-Mounted touchpad (thermostat or stand-alone display)
HID (proprietary device)
PDA (3rd party HID, with software)
Laptop/PC
none
Other
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
Functions Available Through Field Interface**:View ParamsChange ParamsChange
Programs/Logic
O&M SupportTAB/Cx Support
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Microprocessor(s) 32 Bit 24 MHz Toshiba
Clock Type
Powered, battery-backed
Battery powered
Powered, no battery backing
None
Other
Clock Synchronization Software adjustable clock synchronization is broadcast across controller network or to specific network segment of controllers.
Volatile Memory (RAM) Capacity DSC-1616: 512 KB
DSC-1212: 127 KB (319 KB w/ Ethernet Option)
DSC-1280: 256 KB (512 KB w/ Ethernet Option)
Volatile Memory (RAM) Uses
RAM use unrestricted
RAM use restricted as shown below
Information Not Provided
Program Execution / Calculation storage
Data / Trends / Alarms storage
Configuration / Parameter storage
Control Programming storage
Others
Is Volatile Memory Supported By Battery? yes
Battery Type(s) Lithium
Battery Life (5+ years)
Backup Battery Operating Time >>72 Hours
Non-Volatile Memory Capacity (EEPROM/Flash)* DSC-1616: 2 MB
DSC-1212: 1 MB
DSC-1280: 1 MB
Non-Volatile Memory Uses
Data / Trends / Alarms / Calculation Storage
Configuration / Parameter Storage
Control Programming Storage
Controller Operating System
Other
Additional Information
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.
Can trend data be stored in this controller? Yes
How many total trend values can be stored? No Hard Limit. Restricted on Object Database and Remaining Memory.
What is the controllers role in trending? The Controller gathers the samples based on whether it is set up as a polling or Change-of-Value style trend log. If polling type is defined then the controller will gather samples at set intervals. Depending on the particular setup the trend can push data to an archiver or the archiver can pull data from the trend.
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller?
When full, does controller automatically send up trend data, overwrite data, or stop logging data? All of those functions and capabilities are definable in the trend log
Programming Method(s) Uses Delta's 'GCL' program editor. GCL is a line-code programming method that uses a simple language-based syntax.
Resident vs Non-Resident Program Execution Program execution in all primary control units is controller resident
Scheduling
Resident/Supervisory. This controller supervises the scheduling of other controllers.
Resident/Stand Alone. This controller contains its own schedule.
Non-Resident. This controller is dependent upon another controller for its schedule.
None. This controller has no scheduling features.
Other
Resident Energy Management
Energy management algorithms for this controller can be custom programmed
Pre-programmed/built-in algorithms available, and are fully editable using custom programming
Pre-Programmed/built-in with limited editing via template-based programming
Controller is not typically used for energy management functions
Others
Specific Pre-Programmed Algorithms Available
None (custom programming only)
None (not applicable)
Optimal Start/Optimal Stop
Peak Demand Limiting/Load Shedding
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.)
Other
Additional Energy Management functions are resident at SI
Additional Programming Functions
DDC Loops (P, PI, PID) PID
Automatic PID Tuning Feature No
Automatical-Dial Alarm Support Available from both the controller and the front-end Operator Workstation.
Does controller perform multiple retries and buffer/store alarm until connection is made? Yes
Are multiple destinations possible? Yes
Upon controller power loss or hardware failure:
Are network communications affected? No
Is loss recognized on/by the network and alarm reported? Yes
DO and AO response?
Outputs fail to a user pre-specified position
Outputs fail to a normal (unpowered) position
Outputs fail to last position
Other
Volatile memory functions?
Lost
Retained for life of backup battery
Other (If battery dies during loss of power, the database is reloaded on power-up from the Eeprom)
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Yes
Automatically reset/synchronize the clock? Yes
Update all monitored functions? Yes
Generate an alarm if backup battery is dead? No
Upon network or communications failure does controller:
Continue to operate standalone? Yes
Operate with last global settings or user-specified value? N.A.
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
Yes. When the secondary network is broken, a token-based peer-to-peer system generates a second token to operate the bus as two peer-to-peer systems.
Does network automatically reconfigure upon restoration? Yes
Does network store 'loss of communications' alarm with time of event? Yes
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? Yes
Internal hardware failure? Yes
Open/shortened sensor? Yes
Others? Yes
 
Control Enclosure Provided - comes with UL94 V0 Rated Plastic Housing.
Power Supply Required
Voltage 24 Vac
VA DSC-1616 (30VA)
DSC-1212 (25VA)
DSC-1146 (14VA-86VA)
DSC-1180 (20VA)
Surge Protection Provided - 2400 Volt Transient on all Terminals
Underwriters Laboratories UL 916 PAZX (Energy Management)
FCC Part 15, Subpart B, Class A
CE 89/336/EEC
LonMark Certified
Yes
No
No - but LonWorks compatible
Information not provided
BACnet (BTL) Certified
Yes
No
Not submitted for testing
Information not provided
Other