DDC Online direct digital controls
Circon - 300 Series  

SCC-300/SCC-310-GPC General Purpose Controller

Secondary Control Units
SCC-300/SCC-310-GPC
Date Last Saved: 1/13/2006 11:46:49 AM

Product Name(s): SCC-300/SCC-310-GPC General Purpose Controller
Product Description: The SCC-300/SCC-310-GPC is a 13-point configurable, general purpose DDC controller.
Product Application(s): Multi-purpose configurable controller with four independent control loops. Typical uses are: unit heater or baseboard heater control, exhaust fan control, lighting control, variable volume and temperature zone control, space static or duct pressure control.
Point Quantity Characteristics
Analog Input (AI): See Below 10k Thermistor
Dry Contact
0-10VDC
Digital Input (DI): N.A.
Universal Input (AI or DI): N.A.
Analog Output (AO): See Below 0-10VDC
Digital Output (DO): See Below Triac (24VAC@0.8A)
Dry Contact (2.0A)
Universal Output (UO):
Other:
Control Unit Model #:AIDIUIDOAOUOOther
SCC-300-GPC 6 5 2
SCC-310-GPC 6 5 2
A/D Converter Resolution
8 bit
10 bit
12 bit
16 bit
Other Information Not Provided
D/A Converter Resolution
6 bit
8 bit
10 bit
No Analog Output
Other Information Not Provided
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
No
Both AO and DO
DO Only
Other
Indicating status LED on each output?
No
AO and DO
AO Only
DO Only
Other
Integral Flow Sensor? N.A.
Integral Damper Actuator? N.A.
Can controller accept occupant override from thermostat? N.A.
Can controller accept occupancy sensor input? N.A.
Expander Boards N.A.
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
(1) Echelon Free Topology Transceiver (FTT-10A) 78 kbps
External Communication Ports, Speeds and Access Devices N.A.
Additional Information (Optional)
Network Accessing Capabilities via Controller
Access controller only
Access controller plus additional controllers on network segment / LAN
Access all controllers on system
No access available on this controller
Other
Controller Access Devices
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Zone-Based Interface Access Information Not Provided
Zone Interface Hardware
Zone-Mounted touchpad (thermostat or stand-alone display)
HID (proprietary device)
PDA (3rd party HID, with software)
Laptop/PC
none
Other Information Not Provided
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
Functions Available Through Field Interface**:View ParamsChange ParamsChange
Programs/Logic
O&M SupportTAB/Cx Support
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Microprocessor(s) Neuron 3150 10 MHz
Clock Type
Powered, battery-backed
Battery powered
Powered, no battery backing
None
Other software implementation
Clock Synchronization Synched up by a master time source via network variable
Volatile Memory (RAM) Capacity Information Not Provided
Volatile Memory (RAM) Uses
RAM use unrestricted
RAM use restricted as shown below
Information Not Provided
Program Execution / Calculation storage
Data / Trends / Alarms storage
Configuration / Parameter storage
Control Programming storage
Others
Is Volatile Memory Supported By Battery? No
Battery Type(s) None
Battery Life N.A.
Backup Battery Operating Time N.A.
Non-Volatile Memory Capacity (EEPROM/Flash)* Information Not Provided
Non-Volatile Memory Uses
Data / Trends / Alarms / Calculation Storage
Configuration / Parameter Storage
Control Programming Storage
Controller Operating System
Other Information Not Provided
Additional Information
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.
Can trend data be stored in this controller? Yes
How many total trend values can be stored? 4 independent trend logs, each capable of storing 12 trend values
What is the controllers role in trending? Controller holds the trend configuration (point to trend, sample interval, criteria for sample, and performs sampling accordingly, recording data in trend log.
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller? Information not provided
When full, does controller automatically send up trend data, overwrite data, or stop logging data? Overwrite oldest data
Programming Method(s) Uses a template-based form of programming. Configuration performed on laptop/PC running LNS network management tool and the device-specific configuration LNS plug-in supplied by Circon.
Resident vs Non-Resident Program Execution All program execution is controller resident.
Scheduling
Resident/Supervisory. This controller supervises the scheduling of other controllers.
Resident/Stand Alone. This controller contains its own schedule. Four schedules
Non-Resident. This controller is dependent upon another controller for its schedule.
None. This controller has no scheduling features.
Other Network variable override
Resident Energy Management
Energy management algorithms for this controller can be custom programmed
Pre-programmed/built-in algorithms available, and are fully editable using custom programming
Pre-Programmed/built-in with limited editing via template-based programming
Controller is not typically used for energy management functions
Others Information Not Provided
Specific Pre-Programmed Algorithms Available
None (custom programming only)
None (not applicable)
Optimal Start/Optimal Stop
Peak Demand Limiting/Load Shedding
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.)
Other Information Not Provided
Additional Energy Management functions are resident at SI
Additional Programming Functions
DDC Loops (P, PI, PID) P, PI
Automatic PID Tuning Feature None
Automatical-Dial Alarm Support Information Not Provided
Does controller perform multiple retries and buffer/store alarm until connection is made? Information Not Provided
Are multiple destinations possible? Information Not Provided
Upon controller power loss or hardware failure:
Are network communications affected? No
Is loss recognized on/by the network and alarm reported? Yes
DO and AO response?
Outputs fail to a user pre-specified position
Outputs fail to a normal (unpowered) position
Outputs fail to last position
Other
Volatile memory functions?
Lost
Retained for life of backup battery
Other
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Yes
Automatically reset/synchronize the clock? Yes, when synchronized by master clock device via network variable
Update all monitored functions? Yes
Generate an alarm if backup battery is dead? No battery
Upon network or communications failure does controller:
Continue to operate standalone? Yes
Operate with last global settings or user-specified value? N.A.
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
Yes
Does network automatically reconfigure upon restoration? No
Does network store 'loss of communications' alarm with time of event? Yes
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? No
Internal hardware failure? No
Open/shortened sensor? No
Others?
 
Control Enclosure Metal(0.8" X 5" X 5.8")
Four sheet metal screws, optional DIN rail adaptor.
Power Supply Required
Voltage 24 VAC or 24 VDC
External transformer required
VA Information Not Provided
Surge Protection 2.0 Amp slow-blow fuse (Bussman GMD-2.0A, Little fuse 23902.0A)
Underwriters Laboratories UL 916 certification for Energy Management Equipment
FCC Part 15, Class B of the FCC rules for Radio Frequency Devices
CE Information Not Provided
LonMark Certified
Yes
No
No - but LonWorks compatible
Information not provided
BACnet (BTL) Certified
Yes
No
Not submitted for testing
Information not provided
Other