DDC Online direct digital controls
Circon - 200 Series  

UHC-201 Terminal Unit HVAC Controller; UHC-201 P Programmable Terminal Unit HVAC Controller

Secondary Control Units
UHC-201 and UHC-201 P
Date Last Saved: 1/26/2004 10:55:32 AM

Product Name(s): UHC-201 Terminal Unit HVAC Controller; UHC-201 P Programmable Terminal Unit HVAC Controller
Product Description: The UHC-201 is a 10-point, LONWORKS compatible, application specific terminal unit controller The UHC-201_P is a 10-point, LONWORKS compatible, programmable terminal unit and small AHU controller.
Product Application(s): UHC-201: One or two, single-damper VAV boxes One, dual-damper VAV box Pressure dependent or independent One and two stage reheat Analog or digital (tri-state damper modulation) UHC-201_P: (fully programmable) Small AHUs and roof top units Boilers Heat pumps Heaters
Point Quantity Characteristics
Analog Input (AI):
Digital Input (DI):
Universal Input (AI or DI): 4 0-10 Vdc
1000 ohm RTD
Dry contact
Analog Output (AO): 2 0-10 Vdc
Digital Output (DO): 4 Triac switch (0.8 Amp @ 24 Vac)
Universal Output (UO):
Other:
A/D Converter Resolution
8 bit
10 bit
12 bit
16 bit
Other
D/A Converter Resolution
6 bit
8 bit
10 bit
No Analog Output
Other 12 bit
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
No
Both AO and DO
DO Only
Other
Indicating status LED on each output?
No
AO and DO
AO Only
DO Only
Other
Integral Flow Sensor?
Integral Damper Actuator?
Can controller accept occupant override from thermostat?
Can controller accept occupancy sensor input?
Expander Boards None
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
(1) - LonTalk with Echelon Free Topology Transceiver (FFT-10) to LON @ 78 Kbps
External Communication Ports, Speeds and Access Devices None
Additional Information (Optional)
Network Accessing Capabilities via Controller
Access controller only
Access controller plus additional controllers on network segment / LAN
Access all controllers on system
No access available on this controller
Other
Controller Access Devices
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Zone-Based Interface Access None. But see CLI-200 local display panel in Architecture form (permits viewing and changing parameters via direct connection to LON network).
Zone Interface Hardware
Zone-Mounted touchpad (thermostat or stand-alone display)
HID (proprietary device)
PDA (3rd party HID, with software)
Laptop/PC
none
Other N/A
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
Functions Available Through Field Interface**:View ParamsChange ParamsChange
Programs/Logic
O&M SupportTAB/Cx Support
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Microprocessor(s) Neuron 3150 chip
Clock Type
Powered, battery-backed
Battery powered
Powered, no battery backing
None
Other
Clock Synchronization Synched up by a master controller elsewhere on LON
Volatile Memory (RAM) Capacity
Volatile Memory (RAM) Uses
RAM use unrestricted
RAM use restricted as shown below
Information Not Provided
Program Execution / Calculation storage
Data / Trends / Alarms storage
Configuration / Parameter storage
Control Programming storage
Others
Is Volatile Memory Supported By Battery? No
Battery Type(s) None
Battery Life None
Backup Battery Operating Time None
Non-Volatile Memory Capacity (EEPROM/Flash)* Information not provided
Non-Volatile Memory Uses
Data / Trends / Alarms / Calculation Storage
Configuration / Parameter Storage (setpoints, parameters, user settings, schedules, etc.)
Control Programming Storage
Controller Operating System
Other
Additional Information
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.
Can trend data be stored in this controller? Yes - Up to 5 individual trends can be configured (5 different sets of trend values)
How many total trend values can be stored? Approx 500 values allocated over the configured trends
What is the controllers role in trending? Trend data is pulled from controller by OWS.
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller?
When full, does controller automatically send up trend data, overwrite data, or stop logging data? If controller trend data buffer fills before being called by archive workstation, old data is overwritten
Programming Method(s) UHC-201: Application specific controller is configurable only. User can select from several personality applications which are downloaded and configured from the OWS.

UHC-201_P: line code
Resident vs Non-Resident Program Execution All program execution is controller resident
Scheduling
Resident/Supervisory. This controller supervises the scheduling of other controllers. UHC-201P
Resident/Stand Alone. This controller contains its own schedule. UHC-201 & UHC-201P
Non-Resident. This controller is dependent upon another controller for its schedule. UFC-201
None. This controller has no scheduling features.
Other
Resident Energy Management
Energy management algorithms for this controller can be custom programmed UHC-201P
Pre-programmed/built-in algorithms available, and are fully editable using custom programming UHC-201P
Pre-Programmed/built-in with limited editing via template-based programming
Controller is not typically used for energy management functions UHC-201
Others
Specific Pre-Programmed Algorithms Available
None (custom programming only)
None (not applicable) UHC-201
Optimal Start/Optimal Stop UHC-201P
Peak Demand Limiting/Load Shedding
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.)
Other PID, 2+Float, UHC-201P
Additional Energy Management functions are resident at SI
Additional Programming Functions
DDC Loops (P, PI, PID) PID
Automatic PID Tuning Feature No
Automatical-Dial Alarm Support No - See SMC-202 in Architecture form
Does controller perform multiple retries and buffer/store alarm until connection is made? No auto-dial alarm
Are multiple destinations possible? No auto-dial alarm
Upon controller power loss or hardware failure:
Are network communications affected? No
Is loss recognized on/by the network and alarm reported? Yes - by SMC-202. Also reports when controller is restored
DO and AO response?
Outputs fail to a user pre-specified position
Outputs fail to a normal (unpowered) position
Outputs fail to last position
Other
Volatile memory functions?
Lost
Retained for life of backup battery
Other
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Yes
Automatically reset/synchronize the clock? Yes
Update all monitored functions? Yes
Generate an alarm if backup battery is dead? No
Upon network or communications failure does controller:
Continue to operate standalone? Yes
Operate with last global settings or user-specified value? N.A.
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
No
Does network automatically reconfigure upon restoration? No
Does network store 'loss of communications' alarm with time of event? No
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? No
Internal hardware failure? No
Open/shortened sensor? No
Others?
 
Control Enclosure Optional
Power Supply Required
Voltage 24 Vac, 50-60Hz
VA 36 VA
Surge Protection No
Underwriters Laboratories UL 916 certification for energy management equipment
FCC FCC Part 15, Subpart J, Level A
CE No. Other: CSA 22.2 #205-M1983, #950-M89
LonMark Certified
Yes
No
No - but LonWorks compatible
Information not provided
BACnet (BTL) Certified
Yes
No
Not submitted for testing
Information not provided
Other