DDC Online direct digital controls
Trane - Tracker Light Commercial System  

Tracer Loop Controller

Primary Control Unit
Tracer Loop Controller
Date Last Saved: 6/6/2006 8:24:10 AM

Product Name(s): Tracer Loop Controller
Product Description: The Tracer Loop Controller (TLC) is a configurable direct digital controller that provides control and monitoring for water-source heat pump systems. System components that can be controlled and monitored included the pump, boiler, tower (open or closed circuit) mixing valve and the individual heat pumps. The TLC can be used for the coordination of geothermal water-source heat pump systems.
Product Application(s): In a communicating system the TLC has the ability to provide features such as automatic heat pump alarming, centralized water-source heat pump reset, loop water temperature optimization, and building freeze protection.
Point Quantity Characteristics
Analog Input (AI): 6 Predefined Inputs:
- Loop Supply Temp
- Loop Return Temp
- Boiler Supply Temp
- Outdoor Air Temp
- Auxiliary/Unoccupied Temp
- Outside Air Relative Humidity
Digital Input (DI): 5 Predefined Inputs:
- System Enable
- System Flow Status
- System Override
- Pump Request
- Load Shed Request
Universal Input (AI or DI): N.A.
Analog Output (AO): 1 Predefined Output:
- Boiler mixing valve
Digital Output (DO): 12 Predefined Outputs:
- Pump 1
- Pump 2
- Tower Damper
- Tower Circulating Pump
- Tower Stage 1
- Tower Stage 2
- Tower Stage 3
- Tower Isolation Valve
- Boiler Enable
- Compressor Enable
- Fresh Air Unit and Occupied Output
- Alarm
Universal Output (UO): N.A.
Other: N.A.
Control Unit Model #:AIDIUIDOAOUOOther
Tracer Loop Controller 6 5 12 1
A/D Converter Resolution
8 bit
10 bit
12 bit
16 bit
Other Not available
D/A Converter Resolution
6 bit
8 bit
10 bit
No Analog Output
Other Not available
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
No
Both AO and DO
DO Only
Other
Indicating status LED on each output?
No
AO and DO
AO Only
DO Only
Other
Integral Flow Sensor? N.A.
Integral Damper Actuator? N.A.
Can controller accept occupant override from thermostat? N.A.
Can controller accept occupancy sensor input? N.A.
Expander Boards N.A.
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
(1) - LonTalk TP/FT-10A (Trane Comm5, proprietary)
External Communication Ports, Speeds and Access Devices Information Not Provided
Additional Information (Optional)
Network Accessing Capabilities via Controller
Access controller only
Access controller plus additional controllers on network segment / LAN
Access all controllers on system
No access available on this controller
Other
Controller Access Devices
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Zone-Based Interface Access N.A.
Zone Interface Hardware
Zone-Mounted touchpad (thermostat or stand-alone display)
HID (proprietary device)
PDA (3rd party HID, with software)
Laptop/PC
none
Other
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
Functions Available Through Field Interface**:View ParamsChange ParamsChange
Programs/Logic
O&M SupportTAB/Cx Support
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Microprocessor(s) Information not provided
Clock Type
Powered, battery-backed
Battery powered
Powered, no battery backing
None
Other Super-capacitor
Clock Synchronization Information Not Provided
Volatile Memory (RAM) Capacity Information Not Provided
Volatile Memory (RAM) Uses
RAM use unrestricted
RAM use restricted as shown below
Information Not Provided
Program Execution / Calculation storage
Data / Trends / Alarms storage
Configuration / Parameter storage
Control Programming storage
Others
Is Volatile Memory Supported By Battery? Information Not Provided
Battery Type(s) Information Not Provided
Battery Life Information Not Provided
Backup Battery Operating Time Information Not Provided
Non-Volatile Memory Capacity (EEPROM/Flash)* Information Not Provided
Non-Volatile Memory Uses
Data / Trends / Alarms / Calculation Storage
Configuration / Parameter Storage
Control Programming Storage
Controller Operating System
Other Information Not Provided
Additional Information
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.
Can trend data be stored in this controller? No
How many total trend values can be stored? N.A.
What is the controllers role in trending? Information Not Provided
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller? N.A.
When full, does controller automatically send up trend data, overwrite data, or stop logging data? N.A.
Programming Method(s) Template based through local display
Resident vs Non-Resident Program Execution Resident
Scheduling
Resident/Supervisory. This controller supervises the scheduling of other controllers.
Resident/Stand Alone. This controller contains its own schedule.
Non-Resident. This controller is dependent upon another controller for its schedule.
None. This controller has no scheduling features.
Other
Resident Energy Management
Energy management algorithms for this controller can be custom programmed
Pre-programmed/built-in algorithms available, and are fully editable using custom programming
Pre-Programmed/built-in with limited editing via template-based programming
Controller is not typically used for energy management functions
Others
Specific Pre-Programmed Algorithms Available
None (custom programming only)
None (not applicable)
Optimal Start/Optimal Stop
Peak Demand Limiting/Load Shedding
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.)
Other
Additional Energy Management functions are resident at SI
Additional Programming Functions
DDC Loops (P, PI, PID) Information Not Provided
Automatic PID Tuning Feature Information Not Provided
Automatical-Dial Alarm Support Information Not Provided
Does controller perform multiple retries and buffer/store alarm until connection is made? Information Not Provided
Are multiple destinations possible? Information Not Provided
Upon controller power loss or hardware failure:
Are network communications affected? No
Is loss recognized on/by the network and alarm reported? Information Not Provided
DO and AO response?
Outputs fail to a user pre-specified position
Outputs fail to a normal (unpowered) position
Outputs fail to last position
Other
Volatile memory functions?
Lost
Retained for life of backup battery
Other Volatile Memory is Retained because the super capacitor maintains a charge.
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Yes
Automatically reset/synchronize the clock? Yes
Update all monitored functions? Yes
Generate an alarm if backup battery is dead?
Upon network or communications failure does controller:
Continue to operate standalone? Yes
Operate with last global settings or user-specified value? N.A.
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
Yes
Does network automatically reconfigure upon restoration? Information Not Provided
Does network store 'loss of communications' alarm with time of event? Information Not Provided
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? Yes
Internal hardware failure? Yes
Open/shortened sensor? Yes
Others?
 
Control Enclosure NEMA-1, powder coated steel
Power Supply Required
Voltage 120/240 VAC
50/60 Hz, 1 phase
VA 3 amps
Surge Protection Meets CE surge requirements for industrial environments
Underwriters Laboratories UL and C-UL 916: Energy Management Equipment
FCC Part 15, Subpart J, Class A: Emissions
CE • EN50081-1: Light industrial Standard; Class B Emission
• EN50082-2: Heavy Industrial Generic Immunity Standard
LonMark Certified
Yes
No
No - but LonWorks compatible
Information not provided
BACnet (BTL) Certified
Yes
No
Not submitted for testing
Information not provided
Other