DDC Online direct digital controls
Alerton - BACtalk  

VLD-362W; VLD-362

Secondary Control Units
VLD Series Controllers
Date Last Saved: 8/1/2012 9:45:59 AM

Product Name(s): VLD-362W; VLD-362
Product Description: The VLD Series SCUs are programmable display controllers with built in temperature and humidity sensors. Each model is programmable but not expandable and can perform standalone or integrated operation.
Product Application(s): VLD-362: communication with zone HVAC equipment (roof top units, fan coil units, heat pumps, etc.). Used where a combination sensor is required in lieu of separate temperature and humidity sensors. VLD-362W: Same as VLD-362 but with integrated wireless capabilities.
Point Quantity Characteristics
Analog Input (AI): N/A
Digital Input (DI): N/A
Universal Input (AI or DI): See below Controlled voltage, current and resistive modes
Analog Output (AO): N/A
Digital Output (DO): See below Normally open contacts with a maxi switch rating of 24 VAC @ 0.5 A (12 VA).

BO-0, BO-2, and BO-5 are powered from the controller transformer.

BO-1, BO-3, and BO-4 are powered from the controller transformer through removable jumper, allowing these to be powered from a separate power source.
Universal Output (UO): See below Auto-detects for 0-10 VDC or 4-20 mA.

Automatically switches from 0-10VDC to 4-20 mA current mode when it detects a load value of less than 500 Ohms.
Other:
Control Unit Model #:AIDIUIDOAOUOOther
VLD-362 3 6 2
VLD-362W 3 6 2
A/D Converter Resolution
8 bit
10 bit
12 bit
16 bit
Other
D/A Converter Resolution
6 bit
8 bit
10 bit
No Analog Output
Other 12 bit
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
No
Both AO and DO
DO Only
Other
Indicating status LED on each output?
No
AO and DO
AO Only
DO Only
Other Display screen
Integral Flow Sensor? N/A
Integral Damper Actuator? N/A
Can controller accept occupant override from thermostat? N/A
Can controller accept occupancy sensor input? N/A
Expander Boards N/A
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
(1) EIA-485 port - BACnet MS/TP LAN @ 9.6 to 76.8 kbps (polling)
External Communication Ports, Speeds and Access Devices N/A
Additional Information (Optional)
Network Accessing Capabilities via Controller
Access controller only
Access controller plus additional controllers on network segment / LAN
Access all controllers on system
No access available on this controller
Other
Controller Access Devices
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Zone-Based Interface Access
Zone Interface Hardware
Zone-Mounted touchpad (thermostat or stand-alone display)
HID (proprietary device)
PDA (3rd party HID, with software)
Laptop/PC
none
Other
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
Functions Available Through Field Interface**:View ParamsChange ParamsChange
Programs/Logic
O&M SupportTAB/Cx Support
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Microprocessor(s) 32-bit
Clock Type
Powered, battery-backed
Battery powered
Powered, no battery backing
None
Other
Clock Synchronization Information not provided
Volatile Memory (RAM) Capacity None
Volatile Memory (RAM) Uses
RAM use unrestricted
RAM use restricted as shown below
Information Not Provided
Program Execution / Calculation storage
Data / Trends / Alarms storage
Configuration / Parameter storage
Control Programming storage
Others
Is Volatile Memory Supported By Battery? Information not provided
Battery Type(s) None
Battery Life N/A
Backup Battery Operating Time N/A
Non-Volatile Memory Capacity (EEPROM/Flash)* Information not provided
Non-Volatile Memory Uses
Data / Trends / Alarms / Calculation Storage
Configuration / Parameter Storage
Control Programming Storage
Controller Operating System
Other
Additional Information
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.
Can trend data be stored in this controller? No
How many total trend values can be stored? N/A
What is the controllers role in trending? Transmitts data to DDC for trending at DDC control center
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller? Information not provided
When full, does controller automatically send up trend data, overwrite data, or stop logging data? Information not provided
Programming Method(s) Information not provided
Resident vs Non-Resident Program Execution Resident
Scheduling
Resident/Supervisory. This controller supervises the scheduling of other controllers.
Resident/Stand Alone. This controller contains its own schedule.
Non-Resident. This controller is dependent upon another controller for its schedule.
None. This controller has no scheduling features.
Other
Resident Energy Management
Energy management algorithms for this controller can be custom programmed
Pre-programmed/built-in algorithms available, and are fully editable using custom programming
Pre-Programmed/built-in with limited editing via template-based programming
Controller is not typically used for energy management functions
Others
Specific Pre-Programmed Algorithms Available
None (custom programming only)
None (not applicable)
Optimal Start/Optimal Stop
Peak Demand Limiting/Load Shedding
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.)
Other
Additional Energy Management functions are resident at SI
Additional Programming Functions
DDC Loops (P, PI, PID) Information not provided
Automatic PID Tuning Feature Information not provided
Automatical-Dial Alarm Support Information not provided
Does controller perform multiple retries and buffer/store alarm until connection is made? Information not provided
Are multiple destinations possible? Information not provided
Upon controller power loss or hardware failure:
Are network communications affected? Information not provided
Is loss recognized on/by the network and alarm reported? Information not provided
DO and AO response?
Outputs fail to a user pre-specified position
Outputs fail to a normal (unpowered) position
Outputs fail to last position
Other Information not provided
Volatile memory functions?
Lost
Retained for life of backup battery
Other N/A
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Information not provided
Automatically reset/synchronize the clock? Information not provided
Update all monitored functions? Information not provided
Generate an alarm if backup battery is dead? N/A
Upon network or communications failure does controller:
Continue to operate standalone? Yes
Operate with last global settings or user-specified value? N.A.
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
No
Does network automatically reconfigure upon restoration? Yes
Does network store 'loss of communications' alarm with time of event? No
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? Yes
Internal hardware failure? Yes
Open/shortened sensor? Yes
Others?
 
Control Enclosure
Power Supply Required
Voltage 24 VAC
VA 17 VA min load (all BOs off)
89 VA max load (all BOs on)
Surge Protection Information not provided
Underwriters Laboratories UL listed for Open Energy Management Equipment (PAZX) under UL Standard for Safety 916
FCC FCC Part 15, Class B
CE EMC Directive (European CE Mark)
LonMark Certified
Yes
No
No - but LonWorks compatible
Information not provided
BACnet (BTL) Certified
Yes
No
Not submitted for testing
Information not provided
Other