DDC Online direct digital controls
Novar - Logic One  

Lingo; EP/2

Primary Control Unit
Lingo and EP/2
Date Last Saved: 1/26/2004 10:55:34 AM

Product Name(s): Lingo; EP/2
Product Description: Lingo is an expandable, programmable primary controller and supervisory interface with 21 on-board I/O (expandable to 128 control modules) and an on-board touch-screen display. Each Lingo can provide global communications support for up to 128 Logic One secondary controllers on the secondary LAN and communicates with other primary controllers and workstations on the primary LAN. It also has a built in modem and a 3.5" disk drive. Can network 32 Lingo's via TSP or Ethernet. EP/2 is an older version of the Lingo, with less memory and processor power and with an on-board keypad and LCD display. The EP/2 is being replaced by the Lingo.
Product Application(s): Lingo (and EP/2) are designed to provide custom control for central plant, HVAC systems, and commercial refrigeration systems, as well as electrical loads such as lighting panels and motor control centers via secondary controllers. Lingo is the largest and most powerful controller in the Novar line and is intended for use with larger installations (typically networked Lingo's in multiple-building or campus applications).
Point Quantity Characteristics
Analog Input (AI): 2 Outdoor light sensor [4-20mA]

OSA Temp [4-20mA]
Digital Input (DI): 3 Demand pulse from utility meter

Phase loss input [contact closure]

Emergency status
Universal Input (AI or DI):
Analog Output (AO):
Digital Output (DO): 1 Relay (AC/DC) - 2A pilot duty rated. Typically used as an emergency system fault.
Universal Output (UO):
Other:
A/D Converter Resolution
8 bit
10 bit
12 bit
16 bit
Other
D/A Converter Resolution
6 bit
8 bit
10 bit
No Analog Output
Other Not Applicable
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
No
Both AO and DO
DO Only
Other
Indicating status LED on each output?
No
AO and DO
AO Only
DO Only
Other
Integral Flow Sensor?
Integral Damper Actuator?
Can controller accept occupant override from thermostat?
Can controller accept occupancy sensor input?
Expander Boards None
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
Primary LAN: Proprietary over Ethernet @ 10 Mbps (peer-to-peer)

NovarNet (Secondary LAN): Proprietary over EIA-485 (shielded twisted pair) @ 9.6 kbps (polling).
External Communication Ports, Speeds and Access Devices EIA-232 port for PC terminal, or printer.

Ethernet is standard. Phone modem and microwave/satellite optional.
Additional Information (Optional)
Network Accessing Capabilities via Controller
Access controller only
Access controller plus additional controllers on network segment / LAN
Access all controllers on system
No access available on this controller
Other
Controller Access Devices
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Zone-Based Interface Access Information not provided
Zone Interface Hardware
Zone-Mounted touchpad (thermostat or stand-alone display)
HID (proprietary device)
PDA (3rd party HID, with software)
Laptop/PC
none
Other Information not provided
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
Functions Available Through Field Interface**:View ParamsChange ParamsChange
Programs/Logic
O&M SupportTAB/Cx Support
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Microprocessor(s) Intel 486
Clock Type
Powered, battery-backed
Battery powered
Powered, no battery backing
None
Other
Clock Synchronization Information not provided
Volatile Memory (RAM) Capacity Lingo: 16 MB RAM

EP/2: 1 MB RAM supporting control functions and 512 kB RAM supporting network functions
Volatile Memory (RAM) Uses
RAM use unrestricted
RAM use restricted as shown below
Information Not Provided
Program Execution / Calculation storage
Data / Trends / Alarms storage
Configuration / Parameter storage
Control Programming storage
Others
Is Volatile Memory Supported By Battery? Yes
Battery Type(s) Information not provided
Battery Life 5 years
Backup Battery Operating Time 1 hour
Non-Volatile Memory Capacity (EEPROM/Flash)* Lingo: 8 MB flash memory
Non-Volatile Memory Uses
Data / Trends / Alarms / Calculation Storage
Configuration / Parameter Storage
Control Programming Storage
Controller Operating System
Other Information not provided
Additional Information
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.
Can trend data be stored in this controller? Information not provided
How many total trend values can be stored? Information not provided
What is the controllers role in trending? Information not provided
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller?
When full, does controller automatically send up trend data, overwrite data, or stop logging data? Information not provided
Programming Method(s) Controllers are shipped pre-programmed for a variety of common HVAC and electrical systems applications and allow parameter and setpoint input by the user. Custom programs are supported, and are typically provided by Novar-trained representatives prior to shipping.
Resident vs Non-Resident Program Execution Program remains resident in controller.
Scheduling
Resident/Supervisory. This controller supervises the scheduling of other controllers.
Resident/Stand Alone. This controller contains its own schedule.
Non-Resident. This controller is dependent upon another controller for its schedule.
None. This controller has no scheduling features.
Other Information not provided
Resident Energy Management
Energy management algorithms for this controller can be custom programmed
Pre-programmed/built-in algorithms available, and are fully editable using custom programming
Pre-Programmed/built-in with limited editing via template-based programming
Controller is not typically used for energy management functions
Others Information not provided
Specific Pre-Programmed Algorithms Available
None (custom programming only)
None (not applicable)
Optimal Start/Optimal Stop
Peak Demand Limiting/Load Shedding
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.)
Other Information not provided
Additional Energy Management functions are resident at SI
Additional Programming Functions
DDC Loops (P, PI, PID) PID
Automatic PID Tuning Feature Information not provided
Automatical-Dial Alarm Support Information not provided
Does controller perform multiple retries and buffer/store alarm until connection is made? Information not provided
Are multiple destinations possible? Information not provided
Upon controller power loss or hardware failure:
Are network communications affected? Information not provided
Is loss recognized on/by the network and alarm reported? Information not provided
DO and AO response?
Outputs fail to a user pre-specified position
Outputs fail to a normal (unpowered) position
Outputs fail to last position
Other Information not provided
Volatile memory functions?
Lost
Retained for life of backup battery
Other Information not provided
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Information not provided
Automatically reset/synchronize the clock? Information not provided
Update all monitored functions? Information not provided
Generate an alarm if backup battery is dead? Information not provided
Upon network or communications failure does controller:
Continue to operate standalone? Information not provided
Operate with last global settings or user-specified value? N.A.
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
Information not provided
Does network automatically reconfigure upon restoration? Information not provided
Does network store 'loss of communications' alarm with time of event? Information not provided
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? Yes
Internal hardware failure? Information not provided
Open/shortened sensor? Information not provided
Others?
 
Control Enclosure Wall mount aluminum enclosure with electrical conduit knockouts.
Power Supply Required
Voltage Lingo and EP/2: 24 Vac
VA Lingo: 40VA

EP/2: 30VA
Surge Protection Provided - All inputs/outputs protected against lightning-induced surge or voltage transients
Underwriters Laboratories UL 916 PAZX (Energy Management)
FCC Information not provided
CE Information not provided
LonMark Certified
Yes
No Information not provided
No - but LonWorks compatible
Information not provided
BACnet (BTL) Certified
Yes
No
Not submitted for testing
Information not provided
Other