KMC Controls - KMC BACnet  

BAC-10000 Series

Secondary Control Units
FlexStat
Date Last Saved: 7/22/2010 1:09:41 PM

Product Name(s): BAC-10000 Series
Product Description: The FlexStat is a controller and sensor in a single encloser. Unit has standard temperature sensing and optional humidity and motion sensing. FlexStat allows for built-in or custom programming.
Product Application(s): Single and Multi-stage packaged, unitary, and split systems. Heat Pumps. Fan Coil Units. Air Handling Units.
Point Quantity Characteristics
Analog Input (AI): See Below 10K ohm thermistors
dry contacts
0-12 VDC
Digital Input (DI): N.A.
Universal Input (AI or DI): N.A.
Analog Output (AO): See Below 4-20 mA at (0-12 VDC)
Digital Output (DO): See Below Relay
Universal Output (UO): N.A.
Other: See Below Integral Temperature Sensor - All Models
Optional Integral Humidity Sensor - Models BAC-10130CW, 11130CW, 10136CW, 11136CW, 10163CW, 11163CW
Optional Motion/Occupancy Sensor - Models BAC-11030CW, 11130CW, 11036CW, 11136CW, 11063CW, 11163CW
Control Unit Model #:AIDIUIDOAOUOOther
BAC-10030CW 3 3 1
BAC-10130CW 3 3 2
BAC-11030CW 3 3 2
BAC-11130CW 3 3 3
BAC-10036CW 3 3 6 1
BAC-10136CW 3 3 6 2
BAC-11036CW 3 3 6 2
BAC-11136CW 3 3 6 3
BAC-10063CW 3 6 3 1
BAC-10163CW 3 6 3 2
BAC-11063CW 3 6 3 2
BAC-11163CW 3 6 3 3
A/D Converter Resolution
8 bit
10 bit
12 bit
16 bit
Other
D/A Converter Resolution
6 bit
8 bit
10 bit
No Analog Output
Other
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
No
Both AO and DO
DO Only
Other
Indicating status LED on each output?
No
AO and DO
AO Only
DO Only
Other
Integral Flow Sensor? N.A.
Integral Damper Actuator? N.A.
Can controller accept occupant override from thermostat? N.A.
Can controller accept occupancy sensor input? N.A.
Expander Boards
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
EIA-485, BACnet MS/TP @ up to 76.8 Kbps
External Communication Ports, Speeds and Access Devices Optional EIA-485 to USB Communicator for PC Connection.
Additional Information (Optional)
Network Accessing Capabilities via Controller
Access controller only
Access controller plus additional controllers on network segment / LAN
Access all controllers on system
No access available on this controller
Other
Controller Access Devices
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Zone-Based Interface Access English-language menus on a 64x128 pixel LCD display with 5 buttons for data selection and entry.
Zone Interface Hardware
Zone-Mounted touchpad (thermostat or stand-alone display)
HID (proprietary device)
PDA (3rd party HID, with software)
Laptop/PC
none
Other
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
Functions Available Through Field Interface**:View ParamsChange ParamsChange
Programs/Logic
O&M SupportTAB/Cx Support
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Microprocessor(s) Information not provided.
Clock Type
Powered, battery-backed
Battery powered
Powered, no battery backing
None
Other Capacitor backup for 72 hours
Clock Synchronization Yes.
Volatile Memory (RAM) Capacity Information not provided
Volatile Memory (RAM) Uses
RAM use unrestricted
RAM use restricted as shown below
Information Not Provided
Program Execution / Calculation storage
Data / Trends / Alarms storage
Configuration / Parameter storage
Control Programming storage
Others
Is Volatile Memory Supported By Battery? No
Battery Type(s) N.A.
Battery Life N.A.
Backup Battery Operating Time N.A.
Non-Volatile Memory Capacity (EEPROM/Flash)* Information not provided
Non-Volatile Memory Uses
Data / Trends / Alarms / Calculation Storage
Configuration / Parameter Storage
Control Programming Storage
Controller Operating System
Other Information not provided
Additional Information Backup power is provided via capacitor for 72 hours.
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.
Can trend data be stored in this controller? Yes.
How many total trend values can be stored? 8 trend objects, each of which holds 256 samples.
What is the controllers role in trending? Information not provided
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller? Information not provided
When full, does controller automatically send up trend data, overwrite data, or stop logging data? Information not provided
Programming Method(s) 10 program objects
5 built-in programs customizable via Control Basis Programming
5 program objects customizable via BACstage or TotalControl Programming
Resident vs Non-Resident Program Execution Resident
Scheduling
Resident/Supervisory. This controller supervises the scheduling of other controllers.
Resident/Stand Alone. This controller contains its own schedule.
Non-Resident. This controller is dependent upon another controller for its schedule.
None. This controller has no scheduling features.
Other
Resident Energy Management
Energy management algorithms for this controller can be custom programmed
Pre-programmed/built-in algorithms available, and are fully editable using custom programming
Pre-Programmed/built-in with limited editing via template-based programming
Controller is not typically used for energy management functions
Others
Specific Pre-Programmed Algorithms Available
None (custom programming only)
None (not applicable)
Optimal Start/Optimal Stop
Peak Demand Limiting/Load Shedding
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.)
Other
Additional Energy Management functions are resident at SI
Additional Programming Functions
DDC Loops (P, PI, PID) 10 PID loop objects
Automatic PID Tuning Feature Information not provided
Automatical-Dial Alarm Support Information not provided
Does controller perform multiple retries and buffer/store alarm until connection is made? Information not provided
Are multiple destinations possible? Information not provided
Upon controller power loss or hardware failure:
Are network communications affected? Information not provided
Is loss recognized on/by the network and alarm reported? Information not provided
DO and AO response?
Outputs fail to a user pre-specified position
Outputs fail to a normal (unpowered) position
Outputs fail to last position
Other Information not provided
Volatile memory functions?
Lost
Retained for life of backup battery 72 hour capacitor backup
Other
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Information not provided.
Automatically reset/synchronize the clock? Yes, if power is restored within 72 hours.
Update all monitored functions? Information not provided.
Generate an alarm if backup battery is dead? N.A.
Upon network or communications failure does controller:
Continue to operate standalone? Yes.
Operate with last global settings or user-specified value? N.A.
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
Information not provided
Does network automatically reconfigure upon restoration? Information not provided
Does network store 'loss of communications' alarm with time of event? Information not provided
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? No.
Internal hardware failure? No.
Open/shortened sensor? No.
Others?
 
Control Enclosure White or light almond enclosure with dot-matrix LCD display and 5 data entry buttons.
Power Supply Required
Voltage 24 VAC
VA 1 VA steady state, up to 3 VA at start up.
Surge Protection Optional KMD-5567 network surge suppressor
Underwriters Laboratories UL 916 Energy Management Equipment
FCC FCC Class B, Part 15, Subpart B
CE
LonMark Certified
Yes
No
No - but LonWorks compatible
Information not provided
BACnet (BTL) Certified
Yes Pending
No
Not submitted for testing
Information not provided
Other