DDC Online direct digital controls
KMC Controls - KMDigital  

WebLite

Primary Control Unit
Web Lite KMD-5270
Date Last Saved: 6/18/2010 4:16:06 PM

Product Name(s): WebLite
Product Description: A primary network controller and/or supervisory interface. The unit has onboard I/O with output override boards. Ethernet port supports 31 PCUs, RS-485 port supports 32 SCUs. Unit has onboard custom animated color graphics and built-in HTTP server for web-enabled access to the BAS.
Product Application(s): HVAC Control
Point Quantity Characteristics
Analog Input (AI): N.A.
Digital Input (DI): N.A.
Universal Input (AI or DI): 8 pulse counting to 1000 Hz
0-5 v DC analog input range
Analog Output (AO): N.A.
Digital Output (DO): N.A.
Universal Output (UO):
Other:
A/D Converter Resolution
8 bit
10 bit
12 bit
16 bit
Other
D/A Converter Resolution
6 bit
8 bit
10 bit
No Analog Output
Other 12 bit
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
No
Both AO and DO
DO Only
Other Option
Indicating status LED on each output?
No
AO and DO
AO Only
DO Only
Other Option
Integral Flow Sensor? N.A.
Integral Damper Actuator? N.A.
Can controller accept occupant override from thermostat? N.A.
Can controller accept occupancy sensor input? N.A.
Expander Boards Models HPO-6701;6702;6703;6704;6705 Output override boards and Expander boards
Expansion Device Model #AIDIUIDOAOUOOther
HPO-6701 (1) Triac w/HOA
HPO-6702 0-10v DC HOA
HPO-6703 1- NO HOA
HPO-6704 4-20mA HOA
HPO-6705 1- NC HOA
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
1- 10baseT proprietary (38.4 Kbps), BACnet/IP or MSTP (10 Mbps)supports 31 primary control units
1- RS-485 proprietary (38.4Kbps)supports 32 secondary control units
External Communication Ports, Speeds and Access Devices 1- RS-232 computer or modem
Additional Information (Optional)
Network Accessing Capabilities via Controller
Access controller only
Access controller plus additional controllers on network segment / LAN
Access all controllers on system
No access available on this controller
Other
Controller Access Devices
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other Via internet - requires browser and Java VM
Zone-Based Interface Access NetView (KMD-1002) on secondary network
Zone Interface Hardware
Zone-Mounted touchpad (thermostat or stand-alone display)
HID (proprietary device)
PDA (3rd party HID, with software)
Laptop/PC
none
Other
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
Functions Available Through Field Interface**:View ParamsChange ParamsChange
Programs/Logic
O&M SupportTAB/Cx Support
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other Via internet - requires browser and Java VM
Microprocessor(s) Information not provided
Clock Type
Powered, battery-backed
Battery powered
Powered, no battery backing
None
Other
Clock Synchronization Information not provided
Volatile Memory (RAM) Capacity 2 M
Volatile Memory (RAM) Uses
RAM use unrestricted
RAM use restricted as shown below
Information Not Provided
Program Execution / Calculation storage
Data / Trends / Alarms storage
Configuration / Parameter storage
Control Programming storage
Others
Is Volatile Memory Supported By Battery? Yes
Battery Type(s) Information not provided
Battery Life 6 hours
Backup Battery Operating Time Information not provided.
Non-Volatile Memory Capacity (EEPROM/Flash)* 2 M Flash
Non-Volatile Memory Uses
Data / Trends / Alarms / Calculation Storage
Configuration / Parameter Storage
Control Programming Storage
Controller Operating System
Other
Additional Information
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.
Can trend data be stored in this controller? Yes
How many total trend values can be stored? (16) trend logs each with 6 analog, digital or virtual elements or points. (16) runtime logs
What is the controllers role in trending? Data storage
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller?
When full, does controller automatically send up trend data, overwrite data, or stop logging data? Information not provided
Programming Method(s) Control Basic
WinControl XL required to edit graphics
Resident vs Non-Resident Program Execution Information not provided
Scheduling
Resident/Supervisory. This controller supervises the scheduling of other controllers.
Resident/Stand Alone. This controller contains its own schedule.
Non-Resident. This controller is dependent upon another controller for its schedule.
None. This controller has no scheduling features.
Other
Resident Energy Management
Energy management algorithms for this controller can be custom programmed
Pre-programmed/built-in algorithms available, and are fully editable using custom programming
Pre-Programmed/built-in with limited editing via template-based programming
Controller is not typically used for energy management functions
Others
Specific Pre-Programmed Algorithms Available
None (custom programming only)
None (not applicable)
Optimal Start/Optimal Stop
Peak Demand Limiting/Load Shedding
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.)
Other
Additional Energy Management functions are resident at SI
Additional Programming Functions
DDC Loops (P, PI, PID) 8 PID loops
Automatic PID Tuning Feature Information not provided
Automatical-Dial Alarm Support Alarm through Internet connection
Does controller perform multiple retries and buffer/store alarm until connection is made? Information not provided
Are multiple destinations possible? Information not provided
Upon controller power loss or hardware failure:
Are network communications affected? Information not provided
Is loss recognized on/by the network and alarm reported? Information not provided
DO and AO response?
Outputs fail to a user pre-specified position
Outputs fail to a normal (unpowered) position
Outputs fail to last position
Other
Volatile memory functions?
Lost
Retained for life of backup battery
Other
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Yes
Automatically reset/synchronize the clock?
Update all monitored functions?
Generate an alarm if backup battery is dead? Information not provided
Upon network or communications failure does controller:
Continue to operate standalone? Yes
Operate with last global settings or user-specified value? N.A.
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
Yes
Does network automatically reconfigure upon restoration?
Does network store 'loss of communications' alarm with time of event?
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? Information not provided
Internal hardware failure? Information not provided
Open/shortened sensor? Information not provided
Others?
 
Control Enclosure
Power Supply Required transformer
Voltage 24 v AC -15%
VA 25 VA +/- 20%
Surge Protection
Underwriters Laboratories UL 916 Energy Management Equipment
FCC FCC Class B, Part 15, Subpart B
CE Information not provided
LonMark Certified
Yes
No
No - but LonWorks compatible
Information not provided
BACnet (BTL) Certified
Yes
No
Not submitted for testing
Information not provided
Other