DDC Online direct digital controls
KMC Controls - KMDigital  

BACnet LAN Controller KMD 5210-001/002

Primary Control Unit
BACnet LAN Controller KMD 5210-001/002
Date Last Saved: 6/18/2010 4:03:18 PM

Product Name(s): BACnet LAN Controller KMD 5210-001/002
Product Description: 5210-001 BACnet 802.3 version 5210-002 BACnet MSTP version The KMDigital BACnet LAN Controllers are general purpose, expandable (to 128 I/O), programmable controllers. All I/O is provided by expander cards and can be customized per application needs. Two subnetworks of 124 SCUs each may be supported. They can operate stand-alone or communicate peer-to-peer with all other KMDigital controllers.
Product Application(s): The BACnet LAN Controller can be used as a primary controller to support secondary controllers and provide BACnet support. It can be used for all general-purpose HVAC applications including air-handling units, chillers/boiler/central plant control and distribution systems, data acquisition, and other related industry applications
Point Quantity Characteristics
Analog Input (AI): N.A.
Digital Input (DI): N.A.
Universal Input (AI or DI): See Below
Analog Output (AO): N.A.
Digital Output (DO): N.A.
Universal Output (UO):
Other:
Control Unit Model #:AIDIUIDOAOUOOther
KMD-5231-001/002 16
KMD-5232-001/002 32
KMD-5233-001/002 48
KMD-5234-001/002 64
KMD-5235-001/002 16 32
KMD-5236-001/002 32 16
KMD-5237-001/002 48 16
KMD-5238-001/002 16 48
KMD-5239-001/002 32 32
KMD-5240-001/002 16 16
KMD-5241-001/002 16
KMD-5242-001/002 32
KMD-5243-001/002 48
KMD-5244-001/002 64
KMD-5230-001
A/D Converter Resolution
8 bit
10 bit
12 bit
16 bit
Other
D/A Converter Resolution
6 bit
8 bit
10 bit
No Analog Output
Other 12 bit
HOA switches provided on each output?
Note: These are also available as an add-on from 3rd party vendors.
No
Both AO and DO
DO Only
Other Available as part of optional output override boards.
Indicating status LED on each output?
No
AO and DO
AO Only
DO Only
Other Available as part of optional output override boards.
Integral Flow Sensor? N.A.
Integral Damper Actuator? N.A.
Can controller accept occupant override from thermostat? N.A.
Can controller accept occupancy sensor input? N.A.
Expander Boards KMD - 5220 Input Module 0-5 VDC, 4-20 mA, On/Off digital
KMD - 5221 Output Module 12 Bit D/A, 0-10 VDC, 1/12 VDC (On/Off) with short protection, status and output LEDs, uses HPO - 6701, 6702, 6703, 6704 or 6705 output override cards
Expansion Device Model #AIDIUIDOAOUOOther
KMD-5220 16
KMD-5221 16
Network Ports, Protocol(s), and Speed(s) Supported
(Note: See 'Architecture' for network details)
(1)-10baseT Ethernet supports up to 31 primary control units.
(2)- EIA 485 ports: Proprietary @ 38.4 kbps (peer-to-peer)
(2)- EIA 232 serial ports
(1)- DB9 serial port
External Communication Ports, Speeds and Access Devices (2)- EIA 232 serial ports for connection to operator workstation
(1)- DB9 serial port for connection to auto-answer/auto-dial modem
Additional Information (Optional)
Network Accessing Capabilities via Controller
Access controller only
Access controller plus additional controllers on network segment / LAN
Access all controllers on system
No access available on this controller
Other
Controller Access Devices
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Zone-Based Interface Access N.A.
Zone Interface Hardware
Zone-Mounted touchpad (thermostat or stand-alone display)
HID (proprietary device)
PDA (3rd party HID, with software)
Laptop/PC
none
Other
*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up').
Standard access functionality is covered in the Architecture and Software sections.
**Does NOT include front-end OI functions. See vendor for specific functions available.
Functions Available Through Field Interface**:View ParamsChange ParamsChange
Programs/Logic
O&M SupportTAB/Cx Support
Laptop/PC
Local Display Panel (controller-mounted)
Local Display Panel (zone-mounted)
Handheld Interface Device (proprietary device)
PDA (3rd-Party HID)
Zone-Based port (details below)
Other
Microprocessor(s) Motorola 68360/32 bit/ 33 MHz
Clock Type
Powered, battery-backed
Battery powered
Powered, no battery backing
None
Other Capacitor-backed
Clock Synchronization Synchronized to 60 Hz power cycle, and/or synched up by OWS.
Volatile Memory (RAM) Capacity 2 MB RM
Volatile Memory (RAM) Uses
RAM use unrestricted
RAM use restricted as shown below
Information Not Provided
Program Execution / Calculation storage
Data / Trends / Alarms storage
Configuration / Parameter storage
Control Programming storage
Others
Is Volatile Memory Supported By Battery? No. Use of a 3rd-party, commercially available uninterruptible power supply (UPS) is recommended.
Battery Type(s) Not applicable
Battery Life Not applicable
Backup Battery Operating Time Not applicable
Non-Volatile Memory Capacity (EEPROM/Flash)* 2 MB Flash
Non-Volatile Memory Uses
Data / Trends / Alarms / Calculation Storage
Configuration / Parameter Storage
Control Programming Storage
Controller Operating System
Other RAM backed up to Flash Memory every 6 hrs
Additional Information Clock capacitor backup is 72 hours and requires no maintenance.

Programming is executed from RAM and is backed in FLASH at 24 hr or closer intervals.
* Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.
Can trend data be stored in this controller? Yes
How many total trend values can be stored? Up to 96 trend reports can be stored consisting of 6 points per report and 255 values per point (for a total of >146000 stored points per controller)
What is the controllers role in trending? Programming resident within controller gathers and stores trend data on-board. Trend data is written to flash daily, or more frequently as programmed in ControlBASIC using "write to flash" command.
Can controller be programmed to 'push' data to archive or are trends 'pulled' from controller?
When full, does controller automatically send up trend data, overwrite data, or stop logging data? If controller trend data buffer fills before being called by archive workstation, old data is overwritten.
Programming Method(s) The PLC-Series controllers use a combination of fill-in template and characteristic pick bars for I/O point, virtual point (VARs), PID control loop, trend log, schedules, and runtime log definition. They use a non-proprietary (open) line-based programming language (ControlBASIC) for operating sequences.
Resident vs Non-Resident Program Execution All program execution is resident. Programming is retained in non-volatile (FLASH) memory. Any calculations temporarily stored in RAM are lost.
Scheduling
Resident/Supervisory. This controller supervises the scheduling of other controllers.
Resident/Stand Alone. This controller contains its own schedule.
Non-Resident. This controller is dependent upon another controller for its schedule.
None. This controller has no scheduling features.
Other
Resident Energy Management
Energy management algorithms for this controller can be custom programmed
Pre-programmed/built-in algorithms available, and are fully editable using custom programming
Pre-Programmed/built-in with limited editing via template-based programming
Controller is not typically used for energy management functions
Others
Specific Pre-Programmed Algorithms Available
None (custom programming only)
None (not applicable)
Optimal Start/Optimal Stop
Peak Demand Limiting/Load Shedding
Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.)
Other
Additional Energy Management functions are resident at SI
Additional Programming Functions Enthalpy and wet-bulb algorithms are built in to the controller logic and can be used as needed.
DDC Loops (P, PI, PID) 64 PID control loops
Automatic PID Tuning Feature Yes (See ControlBASIC Software form for further detail)
Automatical-Dial Alarm Support Available from controller.
Does controller perform multiple retries and buffer/store alarm until connection is made? Yes. Buffering for up to 128 alarms and 50 messages.
Are multiple destinations possible? Yes
Upon controller power loss or hardware failure:
Are network communications affected? No
Is loss recognized on/by the network and alarm reported? Yes
DO and AO response?
Outputs fail to a user pre-specified position
Outputs fail to a normal (unpowered) position
Outputs fail to last position
Other
Volatile memory functions?
Lost
Retained for life of backup battery
Other Retained if recommended UPS is used
Upon restoration of power does the controller:
Auto-reboot without operator intervention? Yes
Automatically reset/synchronize the clock? Yes. The LAN Controller will also automatically reset clocks across the networks. Use of at least one Local or LAN controller is required to reset clocks across a KMD subnet bus.
Update all monitored functions? Yes
Generate an alarm if backup battery is dead? N.A.
Upon network or communications failure does controller:
Continue to operate standalone? Yes
Operate with last global settings or user-specified value? N.A.
Do broken network segments continue to communicate within the remaining segment?
(Note: May depend on proper termination of segments for higher speed networks.)
Yes. When the network is broken a token-based peer-to-peer system generates a second token to operate the bus as two peer-to-peer systems.
Does network automatically reconfigure upon restoration? Yes - restored controller generates new token.
Does network store 'loss of communications' alarm with time of event? Yes - at OWS
Additional Information (optional)
Self Test Diagnostics
Does controller have internal self-test diagnostics to check:
Processor failure? No.
Internal hardware failure? No.
Open/shortened sensor? Yes.
Others? Outputs short circuit protected
 
Control Enclosure UL Assemblies available.
Power Supply Required
Voltage 120/240 volt pwer supply
Power for expansion cards is provided with optional 24Vac power supply
VA Depends on model # of assembly
Surge Protection Network lightning protection available from manufacturer as an option. Surge protection for up to 230 VAC is integral for inputs and communication lines.
Underwriters Laboratories UL listed.
FCC FCC Class B, Part 15, Subpart B
CE Information not provided.
LonMark Certified
Yes
No
No - but LonWorks compatible
Information not provided
BACnet (BTL) Certified
Yes
No
Not submitted for testing
Information not provided
Other